INSTALLING DUCT COLLARS

IO-DV090

IO-DV090

WWW.CLEANCOMFORT.COM

7

Attach three white plates 

using three #8 screws 

provided to create a 10" plug

Attach the 10" plug to rear 

of the dehumidifier using  

six #8 screws

Attach the second 10" duct 

collar as you did the first. 

Using six #8 screws provided.

90° Flow

Step 3.

 Choose desired orientation for  

10

"

 diameter supply duct collar:

A. Straight through (180°) flow

B. Upward, out of the top (90°) flow

Remove the 10" circular knock out from top panel  

of dehumidifier using side cutters.

-OR-

Recycle three plates and nine extra screws.  

These are only used for 90° flow option

.

180° Flow

Attach the second 10" duct collar as you did the first.  

Use six #8 screws provided.

Ducting for Dehumidification

For the ideal installation, draw air from the central part of 

the home and return it to the isolated areas of the home 

like the bedrooms, den, utility room, or family room. Be 

sure to utilize as many of these remote rooms as possible 

and not just one location. The ductwork of the existing 

HVAC system can be used to supply air to the home. If 

the existing supply goes to isolated areas of the home, 

discharge the supply from the DV090 into the supply duct 

of the existing HVAC system. If the existing heating system 

incorporates a central supply, installation of a separate 

supply duct from the DV090 to each isolated area is 

recommended. 

Содержание DV090

Страница 1: ...l the incoming air stream below its dew point This cooled and drier air is used to pre cool the incoming air stream resulting in increased overall efficiency After the pre cooling stage the processed air is reheated by passing through the condenser coil Fresh Air Ventilation Optional Fresh outdoor air may be ducted to the dehumidifier This provides fresh air to dilute indoor pollutants and repleni...

Страница 2: ... Daikin North America LLC All rights reserved INTRODUCTION 1 SAFETY PRECAUTIONS 3 INTENDED APPLICATION 3 REGISTRATIONS 3 OPTIONAL PARTS LIST 3 SPECIFICATIONS 3 INSTALLATION 3 Installation Considerations 4 Power Accessibility 4 Space 4 Low Voltage Wiring 4 Back Draft Damper 4 Support Structure and Suspension 4 Electrical Requirements 4 Condensate Water Removal 5 Lifting Condensate 5 Condensate Pump...

Страница 3: ...apacity 90 Pints Day 43 L Day Efficiency 5 3 pints kWhr 2 5 L kWhr Duct Connections 6 Round Inlet 10 Round Inlet 10 Round Outlet Air Filter Efficiency MERV 11 Standard 65 Efficient ASHRAE Dust Spot Test Size 14 X 14 x1 Power Cord 8 ft 2 4 m Drain Connection 3 4 Threaded FNPT Refrigerant Type R410a Refer to manufacturers label for more information Dimensions Unit Shipping Width 15 39 cm 18 47 cm He...

Страница 4: ...o the unit Allow a minimum 15 clear ance to the side of the unit to allow for filter removal and replacement Low Voltage Wiring Unit location should be in an area where field wiring the remote controls low voltage to the unit will be possible Back Draft Damper It is recommended that a backdraft damper be used in the supply duct of the DV090 especially when con necting to the supply ducting system ...

Страница 5: ...he remote controls of the DV090 are powered by a low voltage circuit 24VAC and must NEVER contact or be connected to a high voltage circuit The control wires leaving the DV090 and the control are numbered and color coded to prevent confusion Some of the control wires leaving the DV090 may not be used with certain control and should be left unconnected with wire nuts taped onto the stripped ends fo...

Страница 6: ...collars to the DV090 Step 1 Attach 6 diameter fresh air ventilation damper if desired Safety Float Switch the DV090 and the dehumidifier will shut off If the blue wire is in series with the Safety Float Switch the compressor will turn off but the DV090 will continue to ventilate or circulate air as normal Contact your local electrician to install the safety float switch directly to the dehumidifie...

Страница 7: ... for 90 flow option 180 Flow Attach the second 10 duct collar as you did the first Use six 8 screws provided Ducting for Dehumidification For the ideal installation draw air from the central part of the home and return it to the isolated areas of the home like the bedrooms den utility room or family room Be sure to utilize as many of these remote rooms as possible and not just one location The duc...

Страница 8: ...performance positively or negatively depending upon the inside and outside air conditions The outside air duct should be connected to the 6 round collar on the front of the DV090 The amount of outside air can be restricted by the blade damper in the 6 collar Fresh Air Supply Air I CAUTION DO NOT draw air directly from the kitchen laundry or isolated basement You may draw air from a basement that i...

Страница 9: ...If you are unsure of your ventilation air requirements or have need for higher air flows consult Technical Support by calling 1 855 239 2665 Figure 5 Attic Installation Installation in a Basement or Crawlspace with an Existing Forced Air HVAC System Crawlspace Installation Install a separate return to the DV090 in a central area of the home Optional Duct the supply from the DV090 to a 10 x 10 x 10...

Страница 10: ...ventilation See Figure 6 Figure 6 Installation with no forced air HVAC system Ducting for High Efficiency Filtration The filter included with the DV090 is a very efficient MERV 11 media filter This filter should be checked every three months and changed every 6 12 months Quiet Installation Consider compression vibration and airflow noise during installation Use of flex duct and or vibration isolat...

Страница 11: ...not used do not connect the white wire to the DVP 4034748 control or damage to the transformer may result I CAUTION DO NOT allow the yellow lead from the unit to contact the red lead or the white lead from the unit or damage to the transformers will result A 40VA transformer is wired between the red white lead and the yellow leads of the DV090 This low voltage power source powers the relay coils w...

Страница 12: ...ty Range Accuracy 10 95 RH 5 Humidity Range Set Point 35 70 RH Auxiliary Relay Capacity 5 Amps 24VAC Temp Range Accuracy 30 90 F 1 32 C 2 Size 4 95 L x 1 06 W x 4 19 H 12 6 cm L x 2 7 cm W x 10 6 cm H Major Operations Digital control of Relative Humidity Digital Set Point Fan Filter Operation Programmable Ventilation Timer Large easy to read backlit LCD display Easy interaction with air handler fa...

Страница 13: ...ic for DV090 Wiring Schematic I WARNING Servicing the DV090 with its high pressure refrigerant system and high voltage circuitry presents a health hazard which could result in death serious bodily injury and or property damage Call your HVAC contractor for servicing or repair of this equipment To replace the filter remove the filter door from the side of the DV090 dehumidifier by gently pulling it...

Страница 14: ...ator and compresses it to a high pressure and temperature to repeat the process Troubleshooting Neither fan nor compressor running Dehumidification is being called for No fan call 1 Unit unplugged or no power to outlet 2 Humidity control set too high 3 Loose connection in internal or control wiring 4 Defective Compressor relay 5 Defective control transformer Compressor is not running Dehumidificat...

Страница 15: ...1 855 239 2665 Refrigerant Charging If the refrigerant charge is lost due to service or a leak a new charge must be accurately weighed in If any of the old charge is left in the system it must be recovered before weighing in the new charge Refer to the unit nameplate for the correct charge weight and refrigerant type Compressor Capacitor Replacement This compressor is equipped with a two terminal ...

Страница 16: ...la tion at the correct times Motorized Ventilation Damper The motorized ventilation damper is controlled by a field supplied ventilation timer such as the Clean Comfort DVP 4034748 control The damper will open when the ventilation timer is activated to allow fresh air into the home through the 6 diameter fresh air inlet supply duct The motorized ventilation damper will remain closed when the venti...

Страница 17: ...allasufficientlylongdrainhosetoconnect thedrainadaptorofthedehumidifiertothecondensate pumpreservoirusingfield suppliedfittings Step 6 Attachadrainhosetothecondensatepump androuteittoafloordrain Step 7 Use a level to ensure the dehumidifier is level before powering up the dehumidifier and the condensate pump Step 8 Plug in the condensate pump and the assembly is completed Annual inspection of a pr...

Страница 18: ...nty A defect under the terms of this limited warranty shall not include problems resulting from Customer s or Customer s employees agents invitees or a third party s misuse improper installation improper design of any system in which the Product is included abuse lack of normal care failure to follow written instructions tampering improper repair or freezing corrosion acts of nature or other cause...

Страница 19: ...IO DV090 WWW CLEANCOMFORT COM 19 Notes ...

Страница 20: ...W CLEANCOMFORT COM IO DV090 2 14 Our continuing commitment to quality products may mean a change in specifications without notice 2014 DAIKIN NORTH AMERICA LLC Houston Texas USA Email info cleancomfort com 1 855 239 2665 ...

Отзывы: