background image

41001292 Iss 1

 

ELECTRICAL CONNECTIONS 

The heater is suitable for connection to a 415 volt 3 phase 50Hz supply.  
With  modification  the  unit  can  also  be  on  a  240  volt  50Hz  supply  by 
linking  terminals  L1,  L2  and  L3  on  the  main  input  terminal  block  and 
connecting to the supply LIVE. 
On full heat setting the load is 9 kW (CA1309S) & 12kW(CA1312S). 
The connections between the unit and remote switch box are shown on 
the rear of this instruction sheet, Fig 8. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

FUSES 

 

The motor and switch circuits are protected by two fuses which 

have a 3 amp rating.  Ensure that any replacement is of the correct size 
and rating. 
 

MAINTENANCE 

ALWAYS  ENSURE  THAT  THE  MAIN  EXTERNAL  ELECTRICITY 
SUPPLY  IS  SWITCHED  OFF  BEFORE  SERVICING  OF  THIS 
SCREEN-ZONE HEATER. 

 

 

To obtain the best results from the heater it is essential to avoid the 

accumulation of dust and dirt within the unit and on the inlet and 
discharge grilles.  Regular cleaning is necessary with particular 
attention to the fronts and backs of the fan motor blades.  Cleaning of 
the fan is best carried out with a soft brush. 
 

CONTROLS

 

 

The units are designed to provide 2 levels of heat ie half heat and 

full heat, together with 2 fan speeds, normal and boost.  The remote 
control box houses 4 switches. The switch plate is marked as shown 
below.  The functions of the switches are as follows:- 
 
SWITCH 1 (left-hand) 

 

ON/OFF 

SWITCH 2 

 

 

FAN SPEED CONTROL 

SWITCH 3 

 

 

½ HEAT ON/OFF 

SWITCH 4 

 

 

½ HEAT ON/OFF 

 

 

 
 
 
 

TO REPLACE A SWITCH IN THE CONTROL BOX 

a)  Switch off the mains supply 
b)  Remove the switch box cover. 
c)  Disconnect the wiring to the switch. 
d)  Release the spring clips and push out the switch. 

e) 

Fit  the  replacement  switch,  reconnect  the  wiring  and  replace  the 

cover.

 

 

 

For safety reasons a good earth connection must ALWAYS be made to the 

unit  and  the  control  box.    On  the  heater  the  earth  terminal  is  adjacent  to  the 
terminal block and is clearly marked with the symbol 

 

The  unit  should  be  wired  in  accordance  with  BS7671  latest  edition 

requirements  for  electrical  installations.    The  installer  should  ensure  that  a 
suitable fused isolating switch is connected in the mains supply. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

THERMAL CUT-OUTS

 

 

There  are  2  thermal cut-outs  protecting the  heater,  positioned  along 

the heater box.  These cut-outs are connected in series and each or both 
may operate in the event of fan failure or restriction to the free flow of air 
through the unit.  The unit is protected by manual type cut-outs which may 
only be  reset by hand  when the  heater is switched OFF and has cooled 
down.    If  the  cut-outs  trip,  check  the  inlet  and  outlet  grilles  for  airflow 
restrictions.  
 

TO RESET THE CUT-OUTS 

a)  The  cut-outs  are  reset  by  switching  OFF  mains  power  to  the 

appliance and allowing the appliance to cool for 20 minutes. 

b)  Remove  the  appliance  lid  and  locate  the  2  cut-outs.    Ensure  mains 

power  is  OFF.    Reset  each  cut-out  by  pressing  the  white  5  mm 
square reset button located on each cut-out.  

c)  Replace appliance lid.  Switch ON the appliance.  The cut-outs will be 

reset.  If the cut-outs trip again a qualified electrician should be 
consulted. 

 

SPARES 

 

It is essential when ordering spares or replacement parts to state the 

model number CA1309S or CA1312S and the serial number on the rating 
place fixed to the top of the unit. 
     In  the  interest  of  progress  the  Company  reserves  the  right  to  vary 
specifications  from  time  to  time  without  notice.    The  material  listed  is 
offered  subject  to  the  Company’s  General  Conditions  of  Sale,  a  copy  of 
which can be obtained on request. 
 
 
 
 
 
 
 
 
 
 

 

MOUNTING 

 

When mounted over a doorway, the unit should be mounted as low as 

possible and not more than 3.4 metres above the floor.  A single unit will 
give adequate coverage for a 1.2 metre doorway.  For wider doorways, 
units may be mounted end to end.  The heater should be mounted so that 
the inlet or outlet air flow are not obstructed in any way.  A clearance of at 
least 300 mm should be maintained around the inlet and outlet grilles. 

 
 

INSTALLATION 

 

Having removed the appliance lid, to acquire these Instructions, also 

ensure that the Remote Control Switch Box, which is packed inside the 
appliance with these Instructions, is removed and retained. 

 

 

The appliance ‘air flow’ and ‘external dimensions’ are shown in Fig 1. 

 

The heater may be mounted in one of several ways ie:- 

 

1.  Wall Mounting 

a.  Using WALL BRACKETS supplied. 
 

Onto a suitable vertical wall or bearers, the 2 wall brackets are 

secured at the centres shown in Fig 2.  The appliance, with 2 upper bolts 
threaded securely into each face, is then fitted onto/between the wall 
brackets as shown in Fig 3.  The lower fixing bolts are then fitted through 
each wall bracket into each side of the appliance. 
 

The upper 2 bolts allow the appliance to be slipped onto, and held by, 

the wall brackets.  The fitting of the lower bolts in each side locks the 
appliance to the brackets. 
 

Tighten-up securely all 3 bolts in each side. 

 

b.  DIRECTLY to a suitable vertical wall or bearers. 
 

Using 4 x No.12 wood screws.  Screw through the holes in the 

appliance case rear, at the centres shown in Fig 4.  Keyhole slots are 
provided for the upper 2 fixing screws, allowing the appliance to be initially 
located.  The lower 2 fixing screws pass through the appliance rear, 
supporting the appliance and preventing any movement up off the upper 2 
screws. 
 

The wall surface to which the appliance is to be mounted must be flat 

to avoid any distortion of the appliance casing. 

 

2.  Suspended/Hanging 

a.  Using Ø20mm CONDUIT. 
 

The appliance may be suspended by Ø20mm conduit via two suitable 

holes provided in the top of the appliance, see Fig 5. 

 

b.   Studding. 
 

The heater offers four M8 threaded holes as shown in Fig 6. from 

which the appliance may be suspended. 

 

 

 

Electrical Data 

CA1309 

CA1312 

CA1309 

CA1312 

Supply voltage 

 

230V single phase 50Hz 

415V three phase 50Hz 

kW 

12 

12 

Total load 

A/pha 

37.5 

50.1 

12.5 

16.7 

Motor power 

184 

Max Running current 

Amps 

0.8 

Internal fuse size amps 

Amps 

External fuse size amps 

A/pha 

40 

63 

16 

20 

Cable terminal size 

 

10mm

Max 

Mains terminal block position 

 

Bottom of base unit 

Terminals L1; N & E 

Bottom of base unit. 

Terminals N; L1; L2 & L3 

Control terminal block cable size 

 

4mm

Max 

Control terminal block position 

 

Bottom of base unit 

Terminals 1-5 

Bottom of base unit. 

Terminals 1-5 

Control terminal block current 

Amps 

0.8 

Отзывы: