5.1  Models for wireless controls 

 
The  heaters  for  wireless  controls,  models 
HE7230RX,  HE7245RX  and  HE7260RX  can  be 
controlled  by  CONSORT  wireless  controller 
CRX1.  The  heaters  will  not  work  without  a 
controller. Each controller has unique identification 
code,  it  can  control  unlimited  number  of  heaters 
and  will  not  interfere  with  other  controllers  within 
the  building.  For  more  details  please  follow  the 
instructions supplied with the controller. 
 
 
 
 
 
 
 
 

5.2  Standard models 

 
 
All standard heaters 
HE7230, HE7245 and HE7260 are supplied with a 
remote switch that gives the following functions; 
On/off & two heat settings. 
 
For thermostatic control a room thermostat of 
appropriate switch rating maybe connected to the 
circuit. The thermostat should be wired between 
the isolator switch and the heater remote switch. 
For HE7245, HE7260 or to control more than one 
HE7230 heaters by a thermostat, a contactor or a 
relay in conjunction with the thermostat should be 
used. 

5. Operation. 

4. Electrical Connections. 

4.4 Electrical connections for wireless control models

 

Fig.8 Heater with terminal cover open

 

Fig.9 Terminal cover detail

 

To switch on the appliance and operate the 
blower, depress the left-hand switch (marked 
“FAN”). 
 
When the centre switch only (marked with a single 
bar) is depressed the heat output is ⅓ of full heat.  
HE7230  - 1kW, HE7245  - 1.5kW, HE7260  - 2kW 
 
When the right hand switch only (marked with a 
double bar) is depressed the heat output is ⅔ of 
full heat. 
 HE7230  - 2kW, HE7245  - 3kW, HE7260  - 4kW 
 
When both the centre switch and 
the right-hand switch are depressed the full heat 
output is available. 
HE7230  - 3kW, HE7245  - 4.5kW, HE7260  - 6kW 

41001456 Iss 01 

Содержание HE7230

Страница 1: ...01 RECESSED WARM CEILING HEATERS CATALOGUE NUMBERS HE7230 HE7245 HE7260 HE7230RX HE7245RX HE7260RX INSTALLATION AND OPERATING MANUAL Consort Equipment Products Limited Thornton Industrial Estate Milford Haven Pembrokeshire SA73 2RT Tel 01646 692172 Fax 01646 695195 Mon to Fri 8 30 am to 3 30 pm Email enquiries consortepl com Web www consortepl com ...

Страница 2: ... the installer should ensure that a suitable isolating switch is connected in the mains supply 1 4 Controller RX models The HE7230RX HE7245RX HE7260RX heaters are supplied without a controller The RX models will not work without the controller See section 5 1 for more details 1 5 Controller standard models The HE7230 HE7245 HE7260 heaters are sup plied with a remote controller The remote control u...

Страница 3: ...ation Sole liability rests with the installer to ensure that protective safety wear such as hand eye ear and head protection is used during installation of the product 1 General Information Do not rest anything especially ladders against the product 1 10 Standards Units conform to the European electrical standard BS EN 60335 2 30 2 Dimensions 41001456 Iss 01 ...

Страница 4: ...s free from vi bration The discharge grille and diffuser assem bly can now be fitted into the ceiling frame 4 1 Electrical Connections These units are suitable for connection to a 230 240 Volt 50 Hz single phase supply The appliance shall be connected to the supply via an appropriate switched fused double pole isolator having a contact separation of greater than 3mm Test for correct operation and ...

Страница 5: ...switch supplied eg BMS then the heat output can be selected by connecting the appropriate terminals WIRED TERMINALS HE7230 HE7245 HE7260 H1 H2 F 3000W 4500W 6000W H1 F 1000W 1500W 2000W H2 F 2000W 3000W 4000W Please note the F terminal must always be connected F Fan H1 Heating element 1 H2 Heating element N Neutral E Earth 41001456 Iss 01 Fig 5 Remote switch terminal side view Fig 4 Mains supply d...

Страница 6: ...The thermostat should be wired between the isolator switch and the heater remote switch For HE7245 HE7260 or to control more than one HE7230 heaters by a thermostat a contactor or a relay in conjunction with the thermostat should be used 5 Operation 4 Electrical Connections 4 4 Electrical connections for wireless control models Fig 8 Heater with terminal cover open Fig 9 Terminal cover detail To s...

Страница 7: ...Thermal cut out The units are protected from overheating in the event of fan failure or an obstruction of the free airflow by thermal cut outs If this happens the thermal cut outs switch off the appliance The ap pliance will not operate until the heater is discon nected from the mains supply and it has cooled down If this fault re occurs again refer to the section 6 4 fault finding 6 Servicing Mai...

Страница 8: ...8 ...

Отзывы: