WS15P Parts and Service Manual 

Page 13 

Problem

Possible Cause

Solution

8. Hard or untreated water is being delivered

a. Bypass valve is open or faulty

a. Fully close bypass valve or replace

b. Media is exhausted due to high water usage

b. Check program settings or diagnostics for 

abnormal water usage

c. Meter not registering

c. Remove meter and check for rotation or 

foreign material

d. Water quality 

fl

 uctuation

d. Test water and adjust program values 

accordingly

e. No regenerant or low level of regenerant in 

regenerant tank

e. Add proper regenerant to tank

f. Control fails to draw in regenerant

f. Refer to Trouble Shooting Guide number 12

g. Insuf

fi

 cient regenerant level in regenerant tank

g. Check re

fi

 ll setting in programming. Check 

re

fi

 ll 

fl

 ow control for restrictions or debris 

and clean or replace

h. Damaged seal/stack assembly

h. Replace seal/stack assembly

i. Control valve body type and piston type mix 

matched

i. Verify proper control valve body type and 

piston type match

j. Fouled media bed

j. Replace media bed

9. Control valve uses too much regenerant

a. Improper re

fi

 ll setting

a. Check re

fi

 ll setting

b. Improper program settings

b. Check program setting to make sure they are 

speci

fi

 c to the water quality and application 

needs

c. Control valve regenerates frequently

c. Check for leaking 

fi

 xtures that may be 

exhausting capacity or system is undersized

10. Residual regenerant being delivered to service

a. Low water pressure

a. Check incoming water pressure – water 

pressure must remain at minimum of 25 psi

b. Incorrect injector size

b. Replace injector with correct size for the 

application

c. Restricted drain line

c. Check drain line for restrictions or debris 

and clean

11. Excessive water in regenerant tank

a. Improper program settings

a. Check re

fi

 ll setting

b. Plugged injector

b. Remove injector and clean or replace

c. Drive cap assembly not tightened in properly

c. Re-tighten the drive cap assembly

d. Damaged seal/ stack assembly

d. Replace seal/ stack

e. Restricted or kinked drain line

e. Check drain line for restrictions or debris 

and or un-kink drain line

f. Plugged backwash 

fl

 ow controller

f. Remove backwash 

fl

 ow controller and clean 

or replace

g. Missing re

fi

 ll 

fl

 ow controller

g. Replace re

fi

 ll 

fl

 ow controller

12. Control valve fails to draw in regenerant

a. Injector is plugged

a. Remove injector and clean or replace

b. Faulty regenerant piston

b. Replace regenerant piston

c. Regenerant line connection leak

c. Inspect regenerant line for air leak

d. Drain line restriction or debris cause excess back 

pressure

d. Inspect drain line and clean to correct 

restriction

e. Drain line too long or too high

e. Shorten length and or height

f. Low water pressure

f. Check incoming water pressure – water 

pressure must remain at minimum of 25 psi

13. Water running to drain

a. Power outage during regeneration

a. Upon power being restored control will 

fi

 nish the remaining regeneration time. 

Reset time of day. 

b. Damaged seal/ stack assembly

b. Replace seal/ stack assembly

c. Piston assembly failure

c. Replace piston assembly

d. Drive cap assembly not tightened in properly

d. Re-tighten the drive cap assembly

Содержание WS15P

Страница 1: ...ETROLEUM JELLY KEROSENE BENZENE GASOLINE ETC WILL DAMAGE PRODUCTS THAT CONTAIN O RINGS OR PLASTIC COMPONENTS EXPOSURE TO SUCH HYDROCARBONS MAY CAUSE THE PRODUCTS TO LEAK DO NOT USE CLACK CONTROL VALVE...

Страница 2: ...Page 2 WS15P Parts and Service Manual...

Страница 3: ...ral Specifications 4 Drive Cap Assembly Pistons Stack Assembly Main Body 5 Regenerant Components 6 Injectors 7 Injector Flow Graphs U S Units 8 Injector Flow Graphs Metric Units 9 Fitting Kits 10 Drai...

Страница 4: ...gpm 15 psi drop 227 lpm 13 6 m3 h Backwash flow rate 43 gpm 25 psi drop 163 lpm 9 8 m3 h Meter Accuracy Flow Range 5 0 75 75 gpm 2 8 284 lpm Inlet Outlet 1 5 Male NPT or BSPT Drain line 1 Male Elbow N...

Страница 5: ...19 O RING 347 1 8 V4400 NPT WS15P NPT BODY ASSEMBLY 1 V4400 BSPT WS15P BSPT BODY ASSEMBLY 9 V4430 01 WS15P FTG ASY QC TO NPT 1 set of 2 V4430 02 WS15P FTG ASY QC TO BSPT 10 V3641 O RING 225 FOR VALVE...

Страница 6: ...15P Regenerant Components 1 Drawing No Order No Description Quantity 1 H4615 RETAINING CLIP 1 2 V3498 WS15 BRINE ELBOW ASY W RFC 1 3 V3195 01 REFILL PORT PLUG ASY 1 4 V4430 04NPT WS15P NPT DRAIN KIT 1...

Страница 7: ...iameter1 Quantity 1 V3010 15B WS1 5 Injector Asy B Violet 12 1 V3010 15C WS1 5 Injector Asy C Red 13 V3010 15D WS1 5 Injector Asy D White 14 V3010 15E WS1 5 Injector Asy E Blue 16 V3010 15F WS1 5 Inje...

Страница 8: ...5 2 2 5 3 20 40 60 80 100 120 Pressure psi Flow Rate gpm Total Slow Rinse Draw ORDER NO V3010 15E BLUE ORDER NO V3010 15B VIOLET ORDER NO V3010 15F YELLOW ORDER NO V3010 15G GREEN 0 5 1 1 5 2 2 5 3 2...

Страница 9: ...200 300 400 500 600 700 800 900 Pressure kPa Flow Rate lpm Slow Rinse Total Draw 2 4 6 8 10 100 200 300 400 500 600 700 800 900 Pressure kPa Flow Rate lpm Total Slow Rinse Draw 2 4 6 8 10 100 200 300...

Страница 10: ...ROL VALVE PRODUCT S ON WATER SUPPLIES THAT CONTAIN HYDROCARBONS SUCH AS KEROSENE BENZENE GASOLINE ETC Clack Order No V4430 01 Description WS15P QC to NPT Fitting Kit Drawing No Order No Description Qu...

Страница 11: ...62 053 5 3 GPM Drain line flow control V3162 065 6 5 GPM Drain line flow control V3162 075 7 5 GPM Drain line flow control V3162 090 9 0 GPM Drain line flow control V3162 100 10 0 GPM Drain line flow...

Страница 12: ...ce meter f Defective PC Board f Replace PC Board 4 Control valve regenerates at wrong time of day a Power outage a Reset time of day If PC Board has battery back up present the battery may be depleted...

Страница 13: ...water pressure water pressure must remain at minimum of 25 psi b Incorrect injector size b Replace injector with correct size for the application c Restricted drain line c Check drain line for restri...

Страница 14: ...t c Loosen main drive gear Press NEXT and REGEN buttons for 3 seconds to resynchronize software with piston position or disconnect power supply from PC Board for 5 seconds and then reconnect d Imprope...

Страница 15: ...ze software with piston position or disconnect power supply from PC Board for 5 seconds and then reconnect d Foreign matter built up on piston and stack assemblies creating friction and drag enough to...

Страница 16: ...Page 16 WS15P Parts and Service Manual...

Страница 17: ...WS15P Parts and Service Manual Page 17...

Страница 18: ...Page 18 WS15P Parts and Service Manual...

Страница 19: ...oved V3190 series of DLFC from table and V3190 XXX drawing 7 6 2020 PAGE 11 All DLFC housings ship without DLFC installed Up to 5 x V3162 XXX DLFC may be installed in V4430 Select 1 5 flow controls fr...

Страница 20: ...shall be limited at its option to replacement or repair of any Softener and Filter Control valve covered by this Limited Warranty Prior to returning a Control Valve OEM must obtain a return goods aut...

Отзывы: