Page 12
WS15P Parts and Service Manual
Troubleshooting Procedures
Problem
Possible Cause
Solution
1. No Display on PC Board
a. No power at electric outlet
a. Repair outlet or use working outlet
b. Control valve Power Adapter not plugged into
outlet or power cord end not connected to PC
board connection
b. Plug Power Adapter into outlet or connect
power cord end to PC Board connection
c. Improper power supply
c. Verify proper voltage is being delivered to
PC Board
d. Defective Power Adapter
d. Replace Power Adapter
e. Defective PC Board
e. Replace PC Board
2. PC Board does not display correct time of day
a. Power Adapter plugged into electric outlet
controlled by light switch
a. Use uninterrupted outlet
b. Tripped breaker switch and/or tripped GFI
b. Reset breaker switch and/ or GFI switch
c. Power outage
c. Reset time of day. If PC Board has battery
back up present the battery may be
depleted. See Front Cover and Drive
Assembly drawing for instructions.
d. Defective PC Board
d. Replace PC Board
3. Display does not indicate that water is
fl
owing.
Refer to user instructions for how the display
indicates water is
fl
owing
a. Bypass valve in bypass position
a. Turn bypass handles to place bypass in
service position
b. Meter is not connected to meter connection on
PC Board
b. Connect meter to three pin connection
labeled METER on PC Board
c. Restricted/ stalled meter turbine
c. Remove meter and check for rotation or
foreign material
d. Meter wire not installed securely into three pin
connector
d. Verify meter cable wires are installed
securely into three pin connector labeled
METER
e. Defective meter
e. Replace meter
f. Defective PC Board
f. Replace PC Board
4. Control valve regenerates at wrong time of day
a. Power outage
a. Reset time of day. If PC Board has battery
back up present the battery may be
depleted. See Front Cover and Drive
Assembly drawing for instructions.
b. Time of day not set correctly
b. Reset to correct time of day
c. Time of regeneration set incorrectly
c. Reset regeneration time
d. Control valve set at ”on 0” (immediate
regeneration)
d. Check programming setting and reset to
NORMAL (for a delayed regen time)
e. Control valve set at ” on 0” (delayed
and/ or immediate)
e. Check programming setting and reset to
NORMAL (for a delayed regen time)
5. Time of day
fl
ashes on and off
a. Power outage
a. Reset time of day. If PC Board has battery
back up present the battery may be
depleted. See Front Cover and Drive
Assembly drawing for instructions.
6. Control valve does not regenerate
automatically when the REGEN button is
depressed and held.
a. Broken drive gear or drive cap assembly
a. Replace drive gear or drive cap assembly
b. Broken Piston Rod
b. Replace piston rod
c. Defective PC Board
c. Defective PC Board
7. Control valve does not regenerate
automatically but
does
when the REGEN button
is depressed and held.
a. Bypass valve in bypass position
a. Turn bypass handles to place bypass in
service position
b. Meter is not connected to meter connection on
PC Board
b. Connect meter to three pin connection
labeled METER on PC Board
c. Restricted/ stalled meter turbine
c. Remove meter and check for rotation or
foreign material
d. Incorrect programming
d. Check for programming error
e. Meter wire not installed securely into three pin
connector
e. Verify meter cable wires are installed
securely into three pin connector labeled
METER
f. Defective meter
f. Replace meter
g. Defective PC Board
g. Replace PC Board
Содержание WS15P
Страница 2: ...Page 2 WS15P Parts and Service Manual...
Страница 16: ...Page 16 WS15P Parts and Service Manual...
Страница 17: ...WS15P Parts and Service Manual Page 17...
Страница 18: ...Page 18 WS15P Parts and Service Manual...