Cla-Val PC-22D Electronic Pump Control Panel 

Installation, Operation & Maintenance Manual 

 

Page | 22 

 
 
 

 
 
 

5.7 

Alarms 

 
Various alarms can be programmed sending indication to SCADA there is a system failure. The 
alarms/actions menu is accessed by using the 5 button keypad. 
 
 
From the home screen, hold down the up 

arrow for more than 2 seconds to 

access the alarms menu. 
 
 

 
 
 
 
Select the “Actions” icon by using the 

button. 

 
 
 

 
 
 
 
Various conditions can be programmed and sent to SCADA. To send a “fault” condition, program an 
alarm as in figure 18. If the fault alarm is off, the variable fault equals 0, if a fault existed the fault variable 
will equal 1. Outputs can be sent to SO1 (terminals 6 & 7) or SO2 (terminals 8 & 9). 
 
 
 
 
 

Figure 17. PC-22D Controller, Alarms/Actions. 

Figure 18. PC-22D Controller, fault alarm programming. 

Содержание PC-22D

Страница 1: ...PC 22D Electronic Pump Controller Installation Maintenance Manual Operation...

Страница 2: ...be fully excluded we always appreciate any information or suggestions for improving the document E Mail info cla val com We wish to point out that the software and hardware terms as well as the trade...

Страница 3: ...ales excise municipal state or any other Government taxes Minimum order charge 75 00 DISCLAIMER OF WARRANTIES AND LIMITATIONS OF LIABILITY The foregoing warranty is exclusive and in lieu of all other...

Страница 4: ...s 4 2 2 Safety Advice 4 3 Product Description 6 3 1 Specifications 6 4 Installation 9 4 1 Unpacking 9 4 2 Mounting the Enclosure 9 4 3 Component Layout 11 4 4 Wiring Connections 12 4 5 Grounding Shiel...

Страница 5: ...cription 1 2 Copyright This Manual including all figures and illustrations is copyright protected Any further use of this Manual by third parties that violate pertinent copyright provisions is prohibi...

Страница 6: ...a Val PC 22D Valve Controller may only be carried out by electrical specialist with sufficient knowledge in automation The specialists must be familiar with the current norms and guidelines for the de...

Страница 7: ...ironment then install the components in an enclosure being resistant to the above mentioned materials Clean tools and materials are imperative for handling the controller Cleaning only with permitted...

Страница 8: ...pump and control valve status Displays time for system to build pressure and for valve to open Contacts for remote or automatic start signal Local pump start pump stop buttons Local emergency stop but...

Страница 9: ...RH non condensing Memory Protection 10 year life lithium battery Power Requirement Power 120VAC 60Hz protected with 5 Amp Fuse Circuit Breaker Motor Starter Contacts 10 amp maximum Valve Solenoid Cont...

Страница 10: ...ing and closing Dead band Adjustable 0 to full scale of set point signal Cycle Time 0 to 60 seconds in 1 sec increments Integral Band Adjustable 0 to 60 seconds Derivative Band Adjustable 0 to 60 seco...

Страница 11: ...must be installed in accordance with the ATEX directive 94 9 EC 4 1 Unpacking Remove enclosure from box Inspect the packaging and contents for damage Report damages if any to the carrier If any part...

Страница 12: ...Cla Val PC 22D Electronic Pump Control Panel Installation Operation Maintenance Manual Page 10 2 PC 22D Enclosure Mounting Dimensions Figure 3 PC 22D Enclosure Mounting Dimensions...

Страница 13: ...List of Components 1 NEMA 4X Enclosure 2 Cla Val VC 22D Controller 3 Power Supply 24VDC 40Watts 4 5A Circuit Breaker 5 5A Fuse Protection 6 2 Mechanical Relays 7 Din Rail 8 Wiring Ducting 9 3 Position...

Страница 14: ...PC 22D requires 110VAC 60Hz alternating current supplied to the enclosure The product is powered via terminal block 4 5 with CAGE CLAMP connections The provided power supply generates the necessary v...

Страница 15: ...Pressure Limit Switch Connections Terminal block 14 15 16 are reserved for a valve position transmitter or another type of 4 20mA device If using a standard pump control valves these terminals will n...

Страница 16: ...t as minimum pressure met If a pressure switch is not used If a pressure switch is not used a jumper must be inserted across terminal block 21 22 4 5 Grounding Shielding Function Grounding increases t...

Страница 17: ...meet the technical specifications in regards to measuring accuracy Connect the cable shield to the ground potential green terminal block This allows induced interference to dissipate and to be kept aw...

Страница 18: ...l PC 22D Electronic Pump Control Panel Installation Operation Maintenance Manual Page 16 4 6 Cabinet Wiring Provided wiring diagrams are intended to be used as reference only Figure 11 Panel Wiring Di...

Страница 19: ...Cla Val PC 22D Electronic Pump Control Panel Installation Operation Maintenance Manual Page 17 Figure 12 Panel Wiring Diagram...

Страница 20: ...mpleted the boot up process the home screen will appear with system indicators and status 1 Visual Indicators Indicator Color Red Color Green Pump Status Pump OFF Pump ON Pressure Switch Pressure mini...

Страница 21: ...been turned on and the time allowed for the valve to open Both timers have a default value of 30 seconds The system timers are access using the 5 button keypad on the controller From the home screen c...

Страница 22: ...e until the pressure switch contact has been made notifying the controller system pressure has been met Once the opening sequence is complete and the system is in normal operation all system indicator...

Страница 23: ...ocal and Remote A local pump stop command shall be initiated by pressing the stop pump button or by opening the remote start contact By initiating this command the pump control valve solenoid will de...

Страница 24: ...wn the up arrow for more than 2 seconds to access the alarms menu Select the Actions icon by using the button Various conditions can be programmed and sent to SCADA To send a fault condition program a...

Страница 25: ...in which an input or output is accessible as three consecutive 16 bit words Remember that Modbus word data is transmitted in Motorola format i e high order byte low order byte Each input output is re...

Страница 26: ...rd 40102 DI1 digital state 1 0 Input value low order word 40103 Status control word 40104 input value high order word 40105 DI1_C counter value Input value low order word 40106 Status control word 401...

Страница 27: ...ust write status control word with b15 set to 1 other bits will NOT be changed high order word of the new value low order word of the new value To clear an override the client must write at least the...

Страница 28: ...not require a pressure switch If this is the case the supplied USB stick has an application with the pressure switch removed Pressure Switch If the alternative program is used a jumper is still requir...

Страница 29: ...the Stop Pump button When pressed DI5 Stop Pump should change from 0 to 1 This is a momentary switch when the Stop Pump button is released the input will change back to 0 e Verify Pressure Switch Cont...

Страница 30: ...Manual Page 28 2 Verify Output Connections i Insert both ice cube relays back into sockets j When the pump starts verify there is a contact closure between 10 11 This is a non powered output from the...

Страница 31: ......

Страница 32: ...rica com www cla val latinamerica com CLA VAL EUROPE Chemin des M sanges 1 CH 1032 Romanel Lausanne Switzerland Phone 41 21 643 15 55 Fax 41 21 643 15 50 E mail cla val cla val ch CLA VAL UK Dainton H...

Отзывы: