Cla-Val PC-22D Electronic Pump Control Panel
Installation, Operation & Maintenance Manual
Page | 24
Address mapping is as follows:
Analog Inputs
40000
Status/control word
40001
input value, high-order word
40002
AI1
Input value, low-order word
40003
Status/control word
40004
input value, high-order word
40005
AI2
Input value, low-order word
40006
.
.
AI3
.
.
40015
Status/control word
40016
input value, high-order word
40017
AI6
Input value, low-order word
40018-40099
Read as zeros
Digital Inputs
40100
Status/control word
40101
input value, high-order word
40102
DI1 (digital state 1/0)
Input value, low-order word
40103
Status/control word
40104
input value, high-order word
40105
DI1_C (counter value)
Input value, low-order word
40106
Status/control word
40107
input value, high-order word
40108
DI1_F (flow value i.e. counter
value over time)
Input value, low-order word
40109
.
.
DI2
.
.
40145-40147
DI6
40148-40150
DI6_C
40151-40153
DI6_F
40154-40199
Read as zeros
Analog Outputs
40200
Status/control word
40201
input value, high-order word
40202
AO1
Input value, low-order word
40203
Status/control word
40204
input value, high-order word
40205
AO2
Input value, low-order word
40206
.
.
AO3
.
.
40209
Status/control word
40210
input value, high-order word
40211
AO4
Input value, low-order word
40212-40299
Read as zeros