background image

X144D-AF e-FlowMeter

Quick Start Installation & Removal Instructions 

Before

3

Step 3: 

•  Remove the e-FlowMeter Sensor/Head Assembly by

pulling straight outward, being careful not to hit the

sensor tip on the Threaded Swivel Insert tube

•  Set Sensor/Head Assembly aside, taking care to

protect the sensor tip

4

Step 4: 

•  

Orient the Installation Tool so that the bevel is

facing downstream, away from the centering

groove as shown in detail drawing, and insert into

the Threaded Swivel Insert

Step-By-Step X144D-AF e-FlowMeter Removal Instructions (continued)

centering groove

5

Step 5: 

•  Once inserted into the Threaded Swivel Insert tube,

the Installation Tool will engage the top face of the

Measurement Cylinder and force it to the 45° position,

as shown above

top view

After

6

Step 7: 

•  Once engaged, use light force to straighten the

measurement cylinder, and then secure the Installation

Tool in place with Locking Collar in locked position

Step 6:  

•  Slide Installation Tool straight out, then rotate 180° so that

the bevel is facing upstream of the valve, which is now

facing the same direction of the centering groove, see above

•  The lip of the Installation Tool will engage the inside of the

Measurement Cylinder as shown in photo

Installation Tool lip

7

Step 8: 

•  Remove Threaded Swivel Insert from the valve tapping with

the Measurement Cylinder straightened

•  Insert body plug into tapping while servicing the e-FlowMeter

8

top view

flow

flow

N-X144D-AF Quick Start, Removal & Wiring  (R-07-2017)