X144D-AF e-FlowMeter

Quick Start Installation & Removal Instructions 

X144D-AF

Flow Display

w

hi

te

br

ow

n

7

8

4-20mA Loop

Power

Circuit Wiring

Standard Wiring 

1

Step-By-Step X144D-AF e-FlowMeter Removal Instructions

CLA-VAL

flow

Isolation Valves

Step 1: Take necessary safety precautions

a) Isolate the control valve

using main line isolation valves

b) Bleed pressure from valve before 

removing the e-FlowMeter

c) Disconnect power to all electronic

devices on valve, including e-FlowMeter 

2

Knurled

Lock

Step 2: 

After isolating the valve, bleeding pressure and

disconnecting electronic devices, hand loosen the 

Knurled Lock from straight threads

call 800.942.6326 for assistance 

or log-on to

www.cla-val.com for more information 

for additional

wiring diagrams,

download N-144

IOM Manual at

www.cla-val.com