background image

 

General Precautions   

1. Before using CPI-500 / CPI-1000, read all instructions and cautionary 

markings on : (1)CPI-500M / 1000M      (2) The batteries    (3) This manual     

2. 

CAUTION 

--To reduce risk of injury, charge only lead-acid type 

rechargeable batteries. Other types of batteries may cause damage and 

injury. 

3. Do not expose Inverter to rain, snow or liquids of any type. Inverter is 

designed for indoor. 

4. Do not disassemble the Inverter. Take it to a qualified service center when 

service or repair is required. 

5. 

WARNING:

 Provide ventilation to outdoors from the battery compartment. 

The battery enclosure should be designed to prevent accumulation and 

concentration of hydrogen gas at the top of the compartment. 

6. 

NEVER 

charge a frozen battery. 

7. Input/output AC wiring must be no less than 18 AWG gauge copper wire 

and rated for 75

o

C or higher. Battery cables must be rated for 75

o

C or 

higher and should be no less than 10AWG gauge. The inner diameter of 

the copper ring terminal which is used to connect battery cables to 

Inverter DC terminals should be no less than 6mm. 

8. Be extra cautious when working with metal tools around batteries. 

Short-circuiting the batteries could cause an explosion. 

9. For battery installation and maintenance: read the battery manufacturer’s 

installation and maintenance instructions prior to operating. 

10. CiTO Power Inverters can be used with fan, bulb, TV, heater, iron, etc. 

Consult local technicians for more advices.   

 

Personnel Precautions 

1. Have plenty of fresh water and soap nearby in case battery acid contacts 

skin, clothing, or eyes. 

2. Avoid touching eyes while working near batteries. 

3. NEVER smoke or allow a spark or flame in vicinity of a battery. 

4. Remove personal metal items such as rings, bracelets, necklaces, and 

watches when working with batteries. Batteries can produce a short-circuit 

current high enough to make metal melt, and could cause severe burns. 

Содержание CPI-1000 Series

Страница 1: ...USER MANUAL CiTO Power INVERTERS Series CPI 500 CPI 1000...

Страница 2: ...es must be rated for 75o C or higher and should be no less than 10AWG gauge The inner diameter of the copper ring terminal which is used to connect battery cables to Inverter DC terminals should be no...

Страница 3: ...is connected to a wall socket utility power goes to connected equipment s and or charges the battery set via charging system In UPS mode Inverter automatically converts battery energy into AC power f...

Страница 4: ...atically and works in mains mode or inverter mode according to input AC source s status When press this button again Inverter will turn off automatically Mains Mode LED The green LED will blink or lig...

Страница 5: ...tor Three station Terminal Block 4 Output Receptacle s 5 Input Voltage Range Selector Input voltage range is defined in specification chapter and output voltage is the same as input voltage in mains m...

Страница 6: ...inal Tighten the M5 nut Do not place anything between the flat part of battery terminal and the battery cable ring terminal or overheating may occur Figure 4 Battery Cable Connections to CPI 500 1000...

Страница 7: ...otal output voltage This voltage MUST match the DC voltage requirements of the CiTO unit or damage may occur to both the CiTO unit and or the batteries z Parallel Connection Wiring batteries in parall...

Страница 8: ...e is disconnected before attempting to connect AC power cables and load to Inverter Step 2 Connect the hot wire black brown of AC input cable to the HOT IN terminal Step 3 Connect the neutral wire whi...

Страница 9: ...Voltage 12Vdc 24Vdc Charging Voltage 13 7V 27 4V Charging Current 8A max 6A max CHARGER Overcharging Protection 14 5V 29V TRANSFER Transfer Time 8ms typical Line mode Green LED blinks or lights stead...

Страница 10: ...connection Mains normal but works in inverter mode Input protector is effective Reset the input protector Alarm buzzer beeps continuously Overload Verify that the load matches the capability specified...

Отзывы: