Gas Piping Information
Check gas rating plate for type of gas to equip the dryer.
Check for altitude elevation of the dryer.
Check utility for proper installation of gas supply line and gas
pressure.
NATURAL GAS ONLY
Check the gas pressure inlet supply to dryer, 11 inches Water Column
Pressure (27.4 mbar) maximum. Check the manifold pressure,
3.5 inches Water Column Pressure (8.8 mbar) (Natural Gas).
LP GAS ONLY
11 inches Water Column Pressure (27.4 mbar) maximum.
CAUTION: Low gas pressure and intermittent gas will
cause gas ignition problems. This will cause inadequate
drying of the clothes load.
The dryer and its individual shut-off valve must be disconnected
from the gas supply piping system during any pressure testing of
that system at test pressures in excess of 1/2 psig (.04 bar).
The dryer must be isolated from the gas supply piping system by
closing its individual manual shut-off valve during any pressure
testing of the gas supply piping system at test pressures equal to
or less than 1/2 psig (.04 bar).
GAS PIPING
NATURAL GAS ONLY
LP GAS ONLY