Page 23
Dryer Installation with Separate Exhaust (Preferred) (Illustration)
DRYER INSTALLATION WITH SEPARATE EXHAUST
(PREFERRED)
For Exhaust Duct less than 14 feet (5 m) and 2 elbows equivalent
and less than 0.3 (8 mm) inches static pressure.
NEVER exhaust the dryer into a chimney.
NEVER install wire mesh screen over the exhaust or make-
up air area.
NEVER exhaust into a wall, ceiling, or concealed space.
1. Make-up air opening from outside the building may enter the
enclosure from the top or side walls.
(See Dryer Make-Up
Air Requirements Chart)
2. Enclosure (plenum) with service door. This separates the
dryer air from the room comfort air. If dryers use room air
instead of outside air, the heat loss can be another 25 Btu/h
(6.3 kcal/h) for each cubic foot per minute (cfm) used.
EXAMPLE:
A 125 lb. dryer with 2000 cfm (3400 m
3
/h) =
heat loss of 50,000 Btu/h (12,600 kcal/h).
3. Zero inches clearance to combustible material allowed on
sides and at points within 4 inches (102 mm) of front on top.
4. Heat loss into laundry room from dryer fronts
only
is about
60 Btu/h (15.2 kcal/h) per square foot.
DRYER INSTALLATION
WITH SEPARATE
EXHAUST (PREFERRED)
Содержание HD125
Страница 9: ...Page 9 125 lb General Dimensions Illustration...
Страница 10: ...Page 10 125 lb Steam Heated Dryer Dimensions Illustration...
Страница 14: ...Page 14 Gas Loop Piping and Gas Supply Piping System Illustrations...
Страница 18: ...Page 18 Steam Piping Installation Illustration...
Страница 20: ...Page 20 Dryer Installation with Multiple Exhaust Illustration...
Страница 27: ...Page 27 Two Timer Models Figures 1 2 and 3 Illustrations...
Страница 35: ...Page 35 DIRECTSPARK IGNITIONOPERATION FLOW CHART...
Страница 37: ...Page 37 Burner Air Inlet Adjustment with Illustration BURNERAIRINLET ADJUSTMENT...
Страница 38: ...Page 38 Basket Alignment for 125 lb Dryers Illustrations...
Страница 66: ...Page 66...