Page 16
1. The installation must conform to
local codes
or in absence of
local codes, with the
National Fuel Gas Code, ANSI Z223 or
the CAN/CGA-B149, Installation Codes.
2. Check with utilities for proper gas pressure and gas supply
line.
3. Check for altitude elevation of the dryer.
4. The dryer and its individual shut-off valve must be
disconnected from the gas supply piping system at test
pressures in excess of 1/2 PSIG (.04 bar).
5. The dryer must be isolated from the gas supply piping system
by closing its individual manual shut-off valve during any
pressure testing of the gas supply piping system, at test
pressures equal to or less than 1/2 PSIG (.04 bar).
NATURAL GAS ONLY
Check the gas pressure inlet supply to the dryer, 11WC
(27.4 bar)Pressure maximum. Check the manifold pressure,
3.5WC (8.8 bar) Pressure inside the dryer.
CAUTION
Low gas pressure and intermittent gas will cause gas ignition
problems and inadequate drying of the clothes load.
Gas Piping Installation
GAS PIPING
INSTALLATION
Содержание HD125
Страница 9: ...Page 9 125 lb General Dimensions Illustration...
Страница 10: ...Page 10 125 lb Steam Heated Dryer Dimensions Illustration...
Страница 14: ...Page 14 Gas Loop Piping and Gas Supply Piping System Illustrations...
Страница 18: ...Page 18 Steam Piping Installation Illustration...
Страница 20: ...Page 20 Dryer Installation with Multiple Exhaust Illustration...
Страница 27: ...Page 27 Two Timer Models Figures 1 2 and 3 Illustrations...
Страница 35: ...Page 35 DIRECTSPARK IGNITIONOPERATION FLOW CHART...
Страница 37: ...Page 37 Burner Air Inlet Adjustment with Illustration BURNERAIRINLET ADJUSTMENT...
Страница 38: ...Page 38 Basket Alignment for 125 lb Dryers Illustrations...
Страница 66: ...Page 66...