To display the current power supply configuration, use the
show environment power
command.
Note
Procedure
Step 1
Start the configuration mode by entering the
configure terminal
command.
Example:
switch#
configure terminal
switch(config)#
Step 2
Specify one of the following power modes by entering the
power redundancy-mode mode
command:
•
For combined mode, include the
combined
keyword.
•
For power supply redundancy mode, include the
ps-redundant
keyword.
•
For input source redundancy mode, include the
insrc_redundant
keyword.
•
For full redundancy mode, include the
redundant
keyword.
Example:
switch(config)#
power redundancy-mode redundant
switch(config)#
Maximum Power Available for 3-kW Power Supplies
The maximum power available for operations depends on the input power from your power source, the number
and output capabilities of your power supplies, and the power redundancy mode that you use. The following
table lists the amount of power available for 3-kW power supplies depending on power inputs, numbers of
power supplies, and the mode used.