When mounting a chassis in any type of rack equipment, ensure that the temperature of the inlet air to the
chassis does not exceed the specified operating temperature of the chassis.
Caution
The distance between the center lines of the mounting holes on the two mounting posts must be 18.31 inches
(46.50 centimeters) ± 0.06 inch (± 0.15 centimeter). The rack-mounting hardware included with the chassis
is suitable for most 19 inches (48.3 centimeters) equipment racks.
Install the chassis on a rack with the following features:
• NEBS-compliant, 19 inches (48.3 centimeters) rack or 23 inches (58.42 centimeters).
• EIA or European Telecommunications Standards Institute (ETSI) hole patterns in the mounting rails.
The required mounting hardware is shipped with the chassis. If the rack on which you plan to install the
chassis has metric-threaded rails, you must provide your own metric-mounting hardware.
• Perforated top and open bottom for ventilation to prevent overheating.
• Leveling feet for stability.
Do not install the device on an enclosed rack because the chassis requires an unobstructed flow of cooling air
to maintain the acceptable operating temperature. If you use an enclosed rack, ensure that the airflow
requirements are maintained as discussed in the
section.
Receive the Device
Each device is shipped in a container that is strapped to a pallet.
Cisco ASR-920-20SZ-M Aggregation Services Router Hardware Installation Guide
21
Prepare for Installation
Receive the Device