RD
K1
Figure 11: Connection of the discharge resistors.
Cleaning the contactors
: In dirty environments (dust, sawdust, rust particles, etc.) vacuum
the contactor periodically.
There is no estimated time frame for cleaning, it depends on the amount of dirt that is inside the
capacitor bank.
5.2.4.
KEY POINTS FOR INSPECTING CAPACITORS
Inspect the cables and terminals. They should not be overheated or blackened.
The terminals must be clean.
The slow discharge resistors must be in good condition. They must not be open or show
signs of burning.
Check the tightness of the capacitor terminals, as shown in
.
Table 5:Torques of the cables to the capacitor terminals.
Cylindrical capacitor
Power terminal torque (Nm)
CLZ FP
2
Prismatic capacitor
Torque
Power terminal (Nm)
Torque
Earth terminal (Nm)
CV
4.49
6.2
CSB
21
6.2
5.2.5.
KEY POINTS FOR INSPECTING THE REGULATOR
Check that the regulator does not show signs of deterioration and the display is lit as normal.
Inspect the cables and terminals. They should be clean and should not be hardened or over-
heated.
Inspect the connections and the insertion of removable power strips:
- The power strips must be well fastened on removable regulators.
- Check that the terminals are tightened properly. The recommended torque is
0.6 Nm
.
20
OPTIM P&P Series
Instruction Manual
Содержание OPTIM 9 P&P-225-440
Страница 1: ...INSTRUCTION MANUAL M063B01 03 19A Low voltage capacitor banks switched by contactors OPTIM P P Series ...
Страница 2: ...2 OPTIM P P Series Instruction Manual ...
Страница 36: ...10 CE CERTIFICATE 36 OPTIM P P Series Instruction Manual ...
Страница 37: ...37 Instruction Manual OPTIM P P Series ...
Страница 38: ...38 OPTIM P P Series Instruction Manual ...
Страница 39: ...39 Instruction Manual OPTIM P P Series ...