70
MYeBOX 150 - MYeBOX 1500
Instruction Manual
Minimum configuration value:
50%
Maximum configuration value:
97%
Note:
Set the value to 0 to stop recording gaps.
Press the
key to confirm.
Use the
and
keys to toggle between the menu's setup screens.
6�3�3�- OUTAGE, INTERRUPTION
This screen is used to configure the threshold value for logging outages, as a percentage of the
rated voltage value.
010%
CORTE / INTERRUPTION
Press the
key to enter edit mode.
Use the
and
keys to write or change the value of the blinking digit.
When the value on the screen is as desired, use the
and
keys to move the editing cur-
sor.
Minimum configuration value:
1%
Maximum configuration value:
20%
Note:
Set the value to 0 to stop recording outages.
Press the
key to confirm.
Use the
and
keys to toggle between the menu's setup screens.
6�3�4�- TRANSIENTS, DISTURB
This screen is used to configure the distortion level coefficient for the detection of transients.
002.0
TRANSITORIO/DISTURB
Press the
key to enter edit mode.
Use the
and
keys to write or change the value of the blinking digit.
When the value on the screen is as desired, use the
and
keys to move the editing cur-
sor.
Minimum configuration value:
1.0
Maximum configuration value:
100.0
Note :
Recommended value 5.0
Note:
Set the value to 0 to stop detecting transients.
Содержание MYeBOX 150
Страница 2: ...2 MYeBOX 150 MYeBOX 1500 Instruction Manual...
Страница 19: ...19 Instruction Manual MYeBOX 150 MYeBOX 1500 11 12 13 14 15 16 17 18 Figure 13 MYeBOX 1500 terminals upper face...
Страница 90: ...90 MYeBOX 150 MYeBOX 1500 Instruction Manual 14 CE CERTIFICATE...
Страница 91: ...91 Instruction Manual MYeBOX 150 MYeBOX 1500...
Страница 92: ...92 MYeBOX 150 MYeBOX 1500 Instruction Manual...
Страница 93: ...93 Instruction Manual MYeBOX 150 MYeBOX 1500...