Características ambientales                 Environmental features

Temperatura de trabajo

Operating temperature

5 ºC ... 40 ºC

Temperatura de almacenamiento

Storage temperature

5 ºC ... 40 ºC

Altitud máxima

Maximum altitude

2000 m

Categoría de la instalación

Installation category

CAT II 600 V PD3

Características mecánicas                     Mechanical features

   

Conexión

Connection

Tipo banana 4 mm / Banana type 4 mm

Dimensiones 

Dimensions

481 x 126 x 69 mm

Embalaje

Packaging

690 x 210 x 85 mm

Peso

Weight

2.2 kg (Pareja / Couple)

Envolvente

Enclosure

Resina celulósica laminada/ 

Laminated cellulosic resin

Normas /  Standard

UNE-EN 61010-031

  

 

CIRCUTOR SAT: 902 449 459 (SPAIN) / (+34) 937 452 919

 

(out of Spain)

Vial Sant Jordi, s/n
08232 - Viladecavalls  (Barcelona)
Tel: (+34) 937 452 900 - Fax: (+34) 937 452 914
e-mail : [email protected]

M319A01-20-20A

Características técnicas / Technical features

Servicio técnico / Technical service 

This manual is a 

GTEST Probe

 installation guide. For further in-

formation, please download the full manual from the 

CIRCUTOR

 

web site: www.circutor.com

IMPORTANT!

The 

GTEST Probe

 measurement electrode is 

an accessory whose sole use is to take step and 

contact measurements with the 

GETEST

 device.

Contact after-sales service if you suspect that the 
device is not working properly. Do not make any 
changes to the product. 
Do not use the product if has been altered or 
damaged.

The manufacturer of the device is not responsible 
for any damage resulting from failure by the user 
or installer to heed the warnings and/or recom-
mendations set out in this manual, nor for damage 
resulting from the use of non-original products or 
accessories or those made by other manufacturers.

1. DESCRIPTION

The 

GTEST Probe

 measurement electrode is an accessory that 

simplifies feed-through and contact voltage measurements by 

replacing the 25 kg weights. The measurement electrodes allow a 

person to use their weight to make the measurement.

Because the 

GETEST

 device can generate up to 600 V~, the 

measurement electrode is properly insulated. For your safety, please 

read the warnings in this guide.

2. USE

IMPORTANT!

Read all warnings carefully before handling and 

using the electrodes.

For use by authorised or specialised personnel only.

Inspect the electrodes before each measurement 

and do not use them if the insulation material is 

damaged or broken.

They should only be used in dry environmental 

conditions. Never use them in the rain.

Keep the electrode surface clean using a soft cloth 

and soapy water.  Keep the electrode dry at all 

times. Never use abrasive cleaning elements.

Do not subject the electrodes to blows or allow 

them to come into contact with sharp objects that 

may degrade the insulation.

Store the electrodes in a dry place sheltered from 

rain, prolonged exposure to sunlight or other 

agents that can degrade the insulation.

Follow the steps below to take step and contact voltage measure-

ments with the 

GETEST

:

1.-

 Connect the electrode terminal to the 

GETEST

 voltage measure-

ment terminal using the cables supplied with the device. 

Note:

 

Never connect the electrode to the current injection terminals.

2.-

 Place the electrodes on the surface, with the metallic side in 

contact with the ground.

3.-

 Keep the electrodes:

- 1 m apart for the 

step voltage

 test (

Figure 1

). 

- 1 m away from the conducting surface to be tested in the 

contact 

voltage

 test (

Figure 2

).

4.-

 For the contact test, use the electrode connecting cable supplied 

with the device.

5.-

 Ensure the electrodes are stable. 

IMPORTANT!

Despite featuring a non-slip design, the electrodes 

can slide on the surface. Make sure they are stable 

before using them. 

6.-

 Stand on the electrodes, stepping inside the marked surface 

(

Figure 3

).

IMPORTANT!

Always wear non-conducting safety footwear when 

using the electrodes.

Always stand inside the marked area.

7.- 

Keep your body in a fixed position that avoids motion during 

the measurements.

IMPORTANT!

Keep an upright and relaxed position while standing 

on the electrodes. 

For a correct measurement, the weight of the 

person must be at least 

50 kg

.

8.-

 Take the measurement.

IMPORTANT!

Do not touch the metal surfaces during the 

measurements.

Never touch the conducting surface to be tested 

during the contact voltage measurement.

3