4�6�15� Programming the digital output
The
CVM-C5
digitaloutputmaybeprogrammedas:
Pulse by n kWh or kvarh (Energy)
:thevaluecorrespondingtotheenergyconsumed
orgeneratedmaybeprogrammed,togenerateapulse�
Alarm condition:
amagnitudemaybeassociatedwiththedigitaloutput,settinga
maximum,minimumanddelayvalueforthetripcondition�
Ifyoudonotwishtoprogramavariable,put00andvalidatewiththe
key�
Pulse programming by n kWh or kvarh
Onthisscreentheenergycodeisselectedbasedon
Table 11
for
theenergyyouwantthepulseoutputtogenerate�
The
keyjumpsbetweenthedifferentoptions�
Table 11: Codes for the different energy types�
Parameter
Code
ActiveEnergyIIITariff1
31
InductiveReactiveEnergyIIITariff1
32
CapacitiveReactiveEnergyIIITariff1
33
ApparentEnergyIIITariff1
48
ActiveEnergyIIIGeneratedTariff1
49
InductiveReactiveEnergyIIIGeneratedTariff1
50
CapacitiveReactiveEnergyIIIGeneratedTariff1
51
ApparentEnergyIIIGeneratedTariff1
52
ActiveEnergyIIITariff2
55
InductiveReactiveEnergyIIITariff2
56
CapacitiveReactiveEnergyIIITariff2
57
ApparentEnergyIIITariff2
58
ActiveEnergyIIIGeneratedTariff2
59
InductiveReactiveEnergyIIIGeneratedTariff2
60
CapacitiveReactiveEnergyIIIGeneratedTariff2
61
ApparentEnergyIIIGeneratedTariff2
62
ActiveEnergyConsumed
(Regardlessofthetariffselected)
99
OnceanEnergycodehasbeenselectedandvalidatedusingthe
keyyoumustenterthe
kilowattsperpulse�