CVM-BDM supply network analyzer
-------- --- Page Nº 6
)
And also the
MAXIMUM POWER DEMAND
: The power demand is
integrated during a prefixed period.
You can select:
a) The parameter to be controlled (it can measure active power
kW
,
apparent power
kVA
or three phase average current
AIII
).
b) The demand period (1 to 60 min.).
This power demand function works with sliding window: shows the
accumulated demand over the last period from "now".
---------------------------------------------------------------------------------------------
)
CVM-BDM is equipped with an internal memory for the collection of main
parameters from the electric network.
By means of the PC see, the user can select the parameters to be save into
memory among all measured by the power meter (instantaneous, maximum and
minimum values). You can also set the data recording period.
2.1.- Other features
-
DIN rail mounting device with low dimensions.
-
True RMS value measurements.
-
Internal memory (1Mbyte)
-
Measurements in all four quadrants.
-
Power demand
-
Memorizes Maximum and Minimum values.
-
2 leds for the indication of CPU and communications performance.
-
Harmonic distortion measurement (THD-V & THD-A ).
-
Individual harmonic current content (Up to the 15
th
)
-
Flicker measurement (PST & WA)
-
Neutral current calculation.