CVM-BDM supply network analyzer
-------- --- Page Nº 10
3.2.- CVM-BDM Connection terminal (see side labels)
Terminal No Designation
Concept
1 - 28
A1 - A2 supply voltage : 230 V a.c.
27 - 26
dep. model
Relay output No. 1 / 1 output of 4- 20 mA
25 - 24
dep. model
Relay output No. 2 / 2 output of 4- 20 mA
23 - 19
Termination
resistor (RT)
240
Ω
resistor: adaptation of the line final
impedance ( bridge 23 -- 22 and 19 -- 20 )
22
21
20
+
GND
--
COM1 CVM-B : RS-485 connection to the PC
22 + --------------> 1 (+)
21 GND --------------> 5 converter
20 -- ---------------> 2 (--) RS-485/RS-232
16
17
18
No used.
No used.
No used.
15
N
NEUTRAL
14
VL3
Voltage phase 3
13
VL2
Voltage phase 2
12
VL1
Voltage phase 1
11 - 10
I L3: s1 - s2
Current phase L3 .../ 5 A
9 - 8
I L2: s1 - s2
Current phase L2 .../ 5 A
7 - 6
I L1: s1 - s2
Current phase L1 ... / 5 A
NOTE:
Current inputs are isolated in the CVM-BDM model