Page No.
18
4.4.1.4.5.
Screen L44 (INFORMATION: INSTANT VALUES)
This screen shows information on the instant values of different electrical magnitudes.
As this data does not correspond to any specific contract but is data general to all, field B will
have the value 0.
Code
Screen
Text
OBIS
Whitout
OBIS
Comments
0.327.0
V1 VOL
0.527.0
V2 VOL
0.727.0
V3 VOL
VOLTAGE PER PHASE
: This shows the instant
current values in each phase.
0.317.0
I1 AMP
0.517.0
I2 AMP
0.717.0
I3 AMP
CURRENT PER PHASE
: This shows the instant
Current values in each phase.
0.337.0 COSFI 1
0.537.0 COSFI 2
0.737.0 COSFI 3
COS Φ PER PHASE
: This shows the instant cos Φ
values in each phase.
0.17.0
P kW
INSTANT ACTIVE POWER
: This shows the total
instant Active Power in each of the three phases
with its sign.
0.37.0
Q kvar.
INSTANT REACTIVE POWER
: This shows the
total instant Reactive Power in each of the three
phases with its sign.
L44
NSTANT
0.137.0
FP 3PH
AVERAGE POWER FACTOR
: This shows the
average instant Power Factor in the three phases.
4.4.1.4.6.
Screen L45 (INFORMATION: COMMUNICATIONS)
This screen shows information on the different parameters of the communications
ports. As this data does not correspond to any specific contract but is data general to all, field
B will have the value 0.
Code
Screen
Text
OBIS
Whitout
OBIS
Comments
0.00.0
OPTIC
OPTICAL SERIES PORT SETTING
:
000000n (009600 speed, n parity)
0.00.1
R1
ELECTRICAL SERIES PORT
SETTING 1
: 000000n (009600 speed,
n parity)
0.00.2
R2
ELECTRICAL SERIES PORT
SETTING 2
: 000000n (009600 speed,
n parity)
L45
COMMUNICATIONS
0.00.3
MODEM
ELECTRICAL SERIES PORT 1
MODEM START UP MODE
: It will
appear as data for the ASDU 142 of
the protocol