Recommended wire (for you reference):
Table 3: Safe carrying capacity of rubber or plastic insulated wire�
Safe carrying capacity of rubber or plastic insulated wire
Specification
Nominal cross
section
Safe carrying capacity
BX
BLX
BV
BLV
1x 1.13 mm
1 mm
2
20 A
18 A
1x 1.37 mm
1.5 mm
2
25 A
22 A
1x 1.76 mm
2.5 mm
2
33 A
25 A
30 A
23 A
1x 2.24 mm
4 mm
2
42 A
33 A
40 A
30 A
1x 2.73 mm
6 mm
2
55 A
42 A
50 A
40 A
7x 1.13 mm
10 mm
2
80 A
55 A
75 A
55 A
7x 1.76 mm
16 mm
2
105 A
80 A
100 A
75 A
7x 2.12 mm
25 mm
2
140 A
105 A
130 A
100 A
7x 2.50 mm
35 mm
2
170 A
140 A
160 A
125 A
19x 1.83 mm
50 mm
2
225 A
170 A
205 A
150 A
19x 2.14 mm
75 mm
2
280 A
225 A
255 A
185 A
19x 2.50 mm
95 mm
2
340 A
280 A
320 A
240 A
Note:
BX(BLX) copper (aluminium) core rubber insulated wire or BV(BLV) copper (aluminium) core PVC plastic
insulated wire, widely used in 500V or less than 500 V AC and DC power distribution system. The temperature for
the data listed in the above table is 35ºC, the safe carrying capacity value for the wire on single cover.
3.3.- DEVICE TERMINALS
Table 4:List of CEM-C5 terminals�
Device terminals
1 :
L(IN)
, Input, connected to the mains phase
20: +,
Impulse output connection
3:
L(OUT)
, Output
21: -,
Impulse output connection
4,6:
N
, Input, connected to neutral
1
4
3
6
21
20
3
1
6
4
21 20
Figure 4:Terminals of the CEM-C5�
Note:
The Neutral wire can be connected to one of N ports or borh.
9
Instruction Manual
CEM-C5
Содержание CEM-C5
Страница 1: ...INSTRUCTION MANUAL M218B01 03 18A Energy Meter CEM C5...
Страница 2: ...2 CEM C5 Instruction Manual...
Страница 13: ...Figure 7 Dimensions of the CEM C5 13 Instruction Manual CEM C5...
Страница 15: ...8 CE CERTIFICATE 15 Instruction Manual CEM C5...
Страница 16: ...16 CEM C5 Instruction Manual...
Страница 17: ...17 Instruction Manual CEM C5...