28
PHASE
NEUTRAL
PE
Minimum
recommended cable
cross sectional area *
150 mm2**
70 mm2
70 mm2
Power input connection - Wiring:
(*) This is the minimum recommended cable cross sectional area for the maximum AC
input current (see datasheet) using multi-core copper cables with three loaded conduc-
tors for installations in conduit in a thermally insulated wall (A2 method according to
IEC-60364-5-52).
The final cross section might be different if the installation method is another one, in any
case, it has to be calculated by the installer, taking into account the cable materials, the
conditions of installation and distances.
(**)
300 mm2
is the maximum cable cross sectional area accepted by the Main circuit
breaker
.
Содержание Raption 150 Compact
Страница 1: ...Installation Manual Raption 150 Compact ...
Страница 2: ......
Страница 4: ......
Страница 18: ...13 Raption 150 Compact Installation Manual TEMPLATE UPPER PART DIMENSIONS ...
Страница 35: ...30 ...
Страница 38: ...33 Raption 150 Compact Installation Manual 6 ...