VECTIOS
POWER TM
PJ
EN-50
Caution: Do not work on any electrical components
without
fi
rst turning o
ff
the main door switch in
the electrical cabinet.
14 - MAINTENANCE
The minimal maintenance operations and their periodicity
will be made in accordance with national regulations.
All work on the unit’s electrical or refrigerant systems must
be carried out by a quali
fi
ed authorised technician. See the
standard EN 378-4.
It is advisable to sign a maintenance contract with the installer
or an approved maintenance company.
14.1 General recommendations
Safety instructions
●
Technicians working on the unit must wear the necessary
safety gear (e.g. gloves, eye protection, insulating clothing,
safety shoes).
●
Similarly, it is recommended that personnel working close
to sources of high noise emission wear ear defenders. The
ear defenders should in no way impede the wearing of other
protective equipment.
●
The surfaces of the compressor and pipes may reach
temperatures of over 100°C and cause burns if touched.
Likewise, the surfaces of the compressor may in some cases
drop to freezing temperatures which can cause frostbite. It is
therefore important to take special care when carrying out
maintenance work.
●
Do not climb on the machine; use a platform to work at the
necessary height.
●
Do not climb on the copper refrigerant pipes.
Preliminary advise
●
Keep the unit clean.
●
To avoid accidents and ensure proper ventilation of the coil,
keep the unit and the space around it clean and clear of clutter.
●
Check the fouling level of the coil.
Oil
Oils for refrigeration units do not pose any health risks if they
are used in compliance with the precautions for use:
●
Avoid unnecessary handling of components lubricated with
oil. Use protective creams.
●
Oils are
fl
ammable and must be stored and handled with care.
Disposable rags or cloths used in cleaning must be kept away
from open
fl
ames and disposed of in the appropriate manner.
●
Containers must be stored with their caps on. Avoid using oil
from an opened container stored under incorrect conditions.
●
Check the oil level and aspect. In case of a colour change,
check the oil quality using a contamination test.
●
In the case of the presence of acid, water or metallic particles,
replace the a
ff
ected circuit oil, as well as the
fi
lter dryer.
●
If all the oil must be emptied, replace it imperatively with new
oil of the same grade as the original oil which has been stored
in a hermetically sealed container until its time of use.
The oil type recommended for these units is:
Copeland 3MAF 32cST, Danfoss POE 160SZ, ICI Emkarate
RL 32CF, Mobil EAL Artic 22CC.
The following table indicates the required volume:
Refrigerant
Only quali
fi
ed personnel must perform a periodic leak testing, in
accordance with the regulation (EC)
No. 517/2014.
●
The frequency of checks is no longer related to the refrigerant
charge but to its global warming potential:
Charge kg x GWP = t CO2e
Carbon dioxide equivalency (t CO2e) is a quantity that
describes, for a given mixture and amount of greenhouse
gas, the amount in tonnes of CO2 that would have the same
global warming potential (GWP).
The number of tonnes of CO2 equivalent (t CO2e) can be
consulted in the following table:
IPJ
0420
0450
0500
0560
0620
0680
Volume (l)
4 x 3,0
2 x 3,0 +
2 x 3,3
4 x 3,3
4 x 3,3
4 x 3,3
4 x 3,3
IPJ
0720
0760
0840
0960
1050
1200
Volume (l) 2 x 3,3 +
2 x 3,6
2 x 3,3 +
2 x 3,6
3 x 3,6 +
1 x 6,1
1 x 3,6 +
3 x 6,1
4 x 6,1
4 x 6,1
IPJ
0420
0450
0500
0560
0620
0680
Charge (kg)
34,0
34,0
34,0
37,0
37,0
37,5
Environ.
impact
(t CO2e)
71,0
71,0
71,0
77,3
77,3
78,3
Main circuits:
IPJ
0720
0760
0840
0960
1050
1200
Charge (kg)
38,0
54,0
56,0
56,0
67,0
68,0
Environ.
impact
(t CO2e)
79,3
112,8
116,9
116,9
139,9
142,0
Cooling recovery circuit (optional):
IPJ
0420
0450
0500
0560
0620
0680
Charge (kg)
5,3
5,3
5,3
6,4
6,4
6,4
Environ.
impact
(t CO2e)
11,1
11,1
11,1
13,4
13,4
13,4
IPJ
0720
0760
0840
0960
1050
1200
Charge (kg)
6,4
7,6
7,6
7,6
11,9
11,9
Environ.
impact
(t CO2e)
13,4
15,9
15,9
15,9
24,8
24,8
Main circuits:
Cooling recovery circuit (optional):
IPJ
0420
0450
0500
0560
0620
0680
Volume (l)
3,0
3,0
3,0
3,3
3,3
3,3
IPJ
0720
0760
0840
0960
1050
1200
Volume (l)
3,3
3,3
3,3
3,3
3,6
3,6