Measurement scopes of the
CP112
on the
scale ±
250
Pa scale depending on the measurement unit.
Standard scale and central zero setting - left-hand switch
To set the type of measurement scope, position switch 4 as shown opposite:
(0/250 Pa)
E.g. 0-250 Pa: Full scale/0
Setting the output - right-hand switch
2
3
Off
Output settings
Unit settings
To set this type of analogue output, position switch 1 of the output as shown opposite.
2
3
Setting the units – right-hand switch
To set a unit of measurement, position switches 2, 3 and 4 of the units as shown in the table below.
3
2
Once the sensor is in position, switch it on and carry out the autozero procedure to ensure the sensor operates
correctly in any position.
MAINTENANCE
Avoid the use of aggressive solvents. When cleaning with formalin-based products (parts or ducts), protect the device
Temperature or temperature and humidity room sensors:
The room sensors are mounted on a wall in the room to be regulated. The sensors are provided at the back of the vertical unit.
For connections, please see the wiring diagram and the recommendations in paragraph 11.3.
- Changeover
control
:
Surface-mounted onto the hydraulic circuit. This option allows the temperature of the water network to be monitored and the
exchanger (coil) to be operated in either cooling or heating mode (summer or winter mode).
-
Supply air low limit
-
Fire thermostat
11 - TECHNICAL CHARACTERISTICS
EN-25 MAGISTER
®