67
67
A condensate drain pump option is available (see technical specifications in paragraph 12), provided that the humidifier option has
not been requested.
If the humidifier option is selected, the discharge must not drain into the unit's drain pan. To have a single discharge for both,
connect the humidifier drain downstream of the unit's drain pan.
Warning:
the condensates from the humidifier can reach 100 °C.
10.2 - Electrical connection
The electrical connections and wiring must be set up as shown on the wiring diagram included with the unit and in accordance with
applicable standards and regulations.
The unit's power supply cable must be determined according to the power of the unit, the length of the cable, the protection, and
the operating mode.
Check that the characteristics of the electrical power supply conform with the indications on the name plate.
Please ensure the unit is connected to earth, and that the power supply is always able to supply the necessary power.
Electrical specifications: Three-phase 400 V power Earth - 50 Hz
Table of currents
CW 40
CW 53
CW 78
CW 100
CW115
Fan motor assembly
Voltage (V)
400
Power (kW)
3,4
6,8
9,3
Current (A)
5,4
10,8
14,7
Control circuit (transformer)
Voltage (V)
24
Current (A)
1
Humidifier (option)
Voltage (V)
400
Power (kW)
6
Current (A)
8,7
Electric heater (option)
Voltage (V)
400
Power (kW)
12
18
24
33,6
33,6
Current (A)
17,4
26
34,6
48,4
48,4
Total current without option
Current (A)
6,4
6,4
11,8
11,8
15,7
Rating of main switch (A)
16
25
Total current with humidifier
Current (A)
15,1
15,1
20,5
20,5
24,4
Rating of main switch (A)
25
40
Total current with electric heater
Current (A)
23,8
32,4
46,4
60,2
64,1
Rating of main switch (A)
40
63
80
Total current all options
Current (A)
32,5
41,1
55,1
68,9
72,8
Rating of main switch (A)
40
63
80
10 - CONNECTIONS
EN-11 MAGISTER
®