GB-17
If a water softener or water treatment system is used, the water hardness should not be less than 40% of the initial
hardness and should never be less than 15°F.
CW 12/18
CW 24 to CW 115
CW 61/70/80/90
Brand/Model
KUET-1D
KUET-2D
KUET-3D
Control voltage
24 V
24 V
Absorbed power in control
circuit
Without valve: 9 VA
With valve: 35 VA
High power circuit voltage
3-ph, 400 V
3-ph, 400 V
High-power circuit current
(A)
3.2 A
8.7 A
Protection rating
10 A
16 A
Max. power
2.25 kW
6 kW
Factory-set power
CW 12: 1.69 kW
CW 18: 2.25 kW
CW 24: 3.1 kW
CW 30: 4.5 kW
CW 35: 4.5 kW
CW 45: 6 kW
CW 61: 6 kW
CW 70: 6 kW
CW 80/90: 6 kW
CW 115: 6 kW
Factory-set steam flow rate
CW 12:
2.25 kg/h (75%)
CW 18:
3 kg/h (100%)
CW 24: 4 kg /h (50%)
CW 30: 6 kg /h (75%)
CW 35: 6 kg /h (75%)
CW 45: 8 kg / (100%)
CW 61: 8 kg /h (100%)
CW 70: 8 kg /h (100%)
CW 80: 8 kg /h (100%)
CW 115: 8 kg /h (100%)
Max. steam flow rate
1.5 to 3 kg/h
5 to 8 kg/h
Water supply pressure
1 to 8 bar
1 to 8 bar
Max. water supply flow rate
0.6 l/min.
0.6 l/min.
Conductivity of supply
water
125 to 1250 µS/cm
Hardness of supply water
pH 7 to 8
pH 7 to 8
Discharge water flow rate
4 l/min.
4 l/min.
Water supply diameter
¾'' G male
¾'' G male
Drain diameter
32 mm
32 mm
On request