No.
Description
Setting
Unit
Display conditions
Access
level
Enumeration
Min.
Max.
Increment
351 Rotary heat recovery unit control
0: C (closed)
1: O (open)
0
1
1
P36 Heat recovery unit = Gradual speed
heat recovery unit
1
356 Electric heater safety thermostat
0: C (closed)
1: O (open)
0
1
1
P31 Elec preheater = with
or P32 Elec heater = 1 on/off stage
or 2 on/off stages
or 1 gradual stage
or 1 gradual stage + 1 on/off stage
1
362 Pump 1 monitoring
0: C (closed)
1: O (open)
0
1
1
P92 Coil 1 pump = With
1
363 Pump 2 monitoring
0: C (closed)
1: O (open)
0
1
1
P93 Coil 2 pump = With
1
370 Building side isolation damper
0: off
1: on
0
1
1
P26 Isolation damper = Outdoor side +
building
or Building side
1
371 Outdoor side isolation damper
0: off
1: on
0
1
1
P26 Isolation damper = Outdoor side +
building
or Outdoor side
1
373 Air intake fan operating-hour meter
0
999999,9
0,1
h
1
374 Air intake fan percentage
0
100
1
%
1
377 Extraction fan operating-hour meter
0
999999,9
0,1
h
1
378 Extraction fan percentage
0
100
1
%
380 AHU operating feedback
0: off
1: on
0
1
1
1
382 Calculated air quality demand
0
100
1
%
P152 Air quality = with
1
384 Mixing damper closing control
0: off
1: on
0
1
1
P27 Mixing damper = With
1
385 Mixing damper opening control
0: off
1: on
0
1
1
P27 Mixing damper = With
1
386 Mixing damper opening percentage
0
100
1
%
P27 Mixing damper = With
1
392 Setpoint 1 / setpoint 2 status
0: setpoint 1
1: setpoint 2
0
1
1
P160 Setpoint 1/setpoint 2 selection =
Time sched/CMS or on/off input only,
or on/off override
1
394 Calculated cooling demand
0
100
1
%
1
395 Calculated heating demand
0
100
1
%
1
398 Cooling block
0: no
1: yes
0
1
1
1
399 Heating block
0: no
1: yes
0
1
1
1
400 Coil 1 Cooling
0
100
1
%
P28 Coil no.1 = mixed or cold water
1
401 Coil 1 Heating
0
100
1
%
P28 Coil no.1 = mixed or hot water
1
404 Coil 2 Cooling
0
100
1
%
P29 Water coil no.2 = cooling or mixed
1
405 Coil 2 Heating
0
100
1
%
P29 Water coil no.2 = heating or mixed
1
410 Stage 1 electric heater
0: off
1: on
0
1
1
P32 Electric heater = 1 on/off stage
or 2 on/off stages
or 1 gradual stage
or 1 gradual stage + 1 on/off stage
1
411 Stage 1 electric heater operating-hour meter
0
999999,9
0,1
h
P32 Electric heater = 1 on/off stage
or 2 on/off stages
or 1 gradual stage
or 1 gradual stage + 1 on/off stage
1
412 Gradual electric heater stage percentage
0
100
1
%
P32 Electric heater =
1 gradual stage
or 1 gradual stage and 1 on/off stage
1
414 Stage 2 electric heater
0: off
1: on
0
1
1
P31 Electric preheater = with
or
(P32 Electric heater = 2 on/off stages
or 1 gradual stage + 1 on/off stage)
1
415 Stage 2 electric heater operating-hour meter
0
999999,9
0,1
h
P31 Electric preheater = with
or
(P32 Electric heater = 2 on/off stages
or 1 gradual stage + 1 on/off stage)
1
420 Electric heater load shedding status
0: inactive
1: active
0
1
1
(P32 Electric heater = 1 on/off stage
or 2 on/off stages
or 1 gradual stage
or 1 gradual stage + 1 on/off stage)
1
421 Electric preheater load shedding status
0: inactive
1: active
0
1
1
P31 = with
422 Changeover status
0: heating
1: cooling
0
1
1
P28 Coil no.1 = mixed or
P29 Coil no.2 = mixed
1
424 Pump 1
0: off
1: on
0
1
1
P92 Coil 1 pump = With
1
425 Pump 1 operating-hour meter
0
999999,9
0,1
h
P92 Coil 1 pump = With
1
8 - PARAMETERS
FLOWAY
EN-56