8.3 - Reading parameter
No.
Description
Setting
Unit
Display conditions
Access
level
Enumeration
Min.
Max.
Increment
300
Calculated intake flow rate setpoint
0
150000
10
m
3
/h
P104 Air intake ventilation control =
Flow rate
1
301
Air intake fan flow rate
0
320000
10
m
3
/h
1
302 Intake fan differential pressure
0
5000
1
Pa
1
304 Intake duct calculated pressure setpoint
0
5000
1
Pa
P104 Air intake ventilation control =
Duct pressure
1
305 Intake duct pressure
0
5000
1
Pa
P104 Air intake ventilation control =
Duct pressure
1
306
Calculated extraction flow rate setpoint
0
150000
10
m
3
/h
P104 Intake ventilation control =
Flow rate
or
P104 Intake ventilation control =
Duct pressure
and
P105 = Exhaust ventilation control =
Flow rate feedback
1
307
Air extraction fan flow rate
0
320000
10
m
3
/h
1
308 Extraction fan differential pressure
0
5000
1
Pa
1
310 Exhaust duct pressure calculated setpoint
0
5000
1
Pa
P104 Intake ventilation control =
Duct pressure
and
P105 Exhaust ventilation control =
Duct pressure
1
311 Exhaust duct pressure
0
5000
1
Pa
P104 Intake ventilation control =
Duct pressure
and
P105 Exhaust ventilation control =
Duct pressure
1
312
Intake filter differential pressure
0
1000
1
Pa
1
313
Exhaust filter differential pressure
0
1000
1
Pa
1
314
Fouled intake filter differential pressure
calculated threshold
0
1000
1
Pa
1
315
Blocked intake filter differential pressure
calculated threshold
0
1000
1
Pa
1
316
Fouled exhaust filter differential pressure
calculated threshold
0
1000
1
Pa
1
317
Blocked exhaust filter differential pressure
calculated threshold
0
1000
1
Pa
1
320 Calculated cooling setpoint
0,0
50,0
0,1
°C
1
321 Calculated heating setpoint
0,0
50,0
0,1
°C
1
322 Supply air temperature
-99.0
99,9
0,1
°C
Last sensor in the direction of airflow
1
323 Fresh air temperature
-99.0
99,9
0,1
°C
1
324 Return air temperature
-99.0
99,9
0,1
°C
1
325 Internal supply air temperature
-99.0
99,9
0,1
°C
(P03 < 2) and ((Number of coils >1)
or (P29 > 0))
or
Number of coils > 0 and P01 = ceiling unit
1
326 Room temperature
-99.0
99,9
0,1
°C
P154 Target temperature selection =
Room
1
327 Heat recovery unit outlet temperature, intake
side
-99,0
99,9
0,1
°C
P38 Temperature sensor upstream of
heat recovery unit = With
1
328 Heat recovery unit pressure drop calculated
threshold
0
345
1
Pa
P37 Differential pressure sensor on the
heat recovery unit = With
1
329 Heat recovery unit DP
0
1000
1
Pa
P37 Differential pressure sensor on the
heat recovery unit = With
1
331 CO
2
air quality
0
2000
1
ppm
P152 Air quality control = With
1
340 Remote control
0: C (closed)
1: O (open)
0
1
1
1
341 Setpoint 1 / Setpoint 2
0: C (closed)
1: O (open)
0
1
1
P160 setpoint 1/setpoint 2 selection =
on/off input or on/off override
1
342 Fire
0: C (closed)
1: O (open)
0
1
1
P24 Fire detection = With
1
345 Mixed coil changeover thermostat
0: C (closed)
1: O (open)
0
1
1
P28 Water coil no.1 = Mixed or
P29 Water coil no.2 = Mixed
and
P162 Changeover selection = On/off input
1
346 Air intake fan control
0: C (closed)
1: O (open)
0
1
1
1
348 Extraction fan control
0: C (closed)
1: O (open)
0
1
1
1
8 - PARAMETERS
EN-55 FLOWAY