8 - PARAMETERS
Here is the list of parameters settable by:
-
The user (access level 1 - no password on alphanumeric terminals, password 1111 on touch screen terminals)
-
The installer (access level 2)
-
The manufacturer (access level 3)
The level 2 password can be requested from your technical support. Some parameters are not always visible and depend on the
machine's configuration.
8.1 - Machine parameters
No.
Description
Setting
Display conditions
Access
level
Enumeration
By default
1
Unit model
3
3
Number of intake EC fans
1 or 2
as per P1
Visible as read-only
3
4
Characteristics of the pressure sensor for the air
intake fan
1: 0-1000 Pa 10V
2: 0-2500 Pa 10V
3: 0-5000 Pa 10V
4: 0-1600 Pa 0.3-5V
5: 0-1000 Pa 0.5-4.5V
6: 0-3000 Pa 0.5-4.5V
as per P1
Visible as read-only
3
5
Coefficient value K for the intake fan
as per P1
Visible as read-only
3
7
Intake filter type
1: M5
2: F7
3: F9
1
3
4: M5 + F7
5: M5 + F9
6: F7 + F9
1
P1 = Classic RHE or Classic PHE or Vertical PHE
3
8
Intake filter coefficient
as per P1
and P7
3
9
Characteristics of the pressure sensor for the air
intake filter
1 : 0-1000 Pa 0,5-4,5V
2 : 0-800 Pa 0,5-4,5V
2
3
11
Number of EC air exhaust fans
1 or 2
as per P1
Visible as read-only
3
12
Characteristics of the pressure sensor for the air
extraction fan
1: 0-1000 Pa 10V
2: 0-2500 Pa 10V
3: 0-5000 Pa 10V
4: 0-1600 Pa 0.3-5V
5: 0-1000 Pa 0.5-4.5V
6: 0-3000 Pa 0.5-4.5V
as per P1
Visible as read-only
3
13
Coefficient value K for the exhaust fan
as per P1
Visible as read-only
3
15
Exhaust filter type
1: M5
2: F7
3: F9
1
3
16
Exhaust filter coefficient
as per P1
and P15
3
17
Characteristics of the pressure sensor for the air
exhaust filter
1 : 0-1000 Pa 0,5-4,5V
2 : 0-800 Pa 0,5-4,5V
2
3
24
Fire detection
0: Without
1: With
0
3
26
Isolation damper
0: Without
1: Outdoor sides
2: Building side
3: O building sides
0
3
27
Mixing damper
0: Without
1: With
0
P1 = Classic RHE
3
28
Coil no.1
0: None
0
3
1: Cold water
P32 Elec heat = Without or 1 on/off stage
or 2 on/off stages
3: Hot water
4: Mixed (water)
P32 Elec heat = Without or 1 on/off stage
or 2 on/off stages
29
Hydraulic coil no.2
0: Without
1: Cooling
2: Heating
4: Mixed (water)
0
3
31
Electric pre-heater
0: Without
1: With
0
P32 = Without or 1 on/off stage or 1 gradual stage
3
32
Electric heater
0: Without
1: 1 on/off stage
0
3
2: 2 On/Off stages
P31 = Without
5: 1 gradual stage
P29 = without
6: 1 gradual stage and 1 On/Off
stage
P29 = Without and P31 = Without
EN-49