CIAT DYNACIAT LG 080 Скачать руководство пользователя страница 59

14.2.7 - 

Unit operation with a free cooling drycooler 

(optional)

14.2.7.1 - Operating principle

The units have been designed to optimize system operation, 

using drycoolers as a free cooling system (method using low 

outdoor air temperatures to chill the water of the air conditioning 

system).
This system allows substantial energy and cost savings, which 

is the most effective when the outdoor air temperature is low.
The TouchPilot control of the unit includes algorithms to permit 

constant automatic optimization of:  

 

-

drycooler fans operation

 

-

water flow rate variation in the loop, 

 

-

cooling capacity (drycooler and chiller can operate 

independently or simultaneously)

 

-

valves positions depending on operating mode.

The control defines the optimal configuration considering water 

set point value, outdoor air temperature and water loop 

temperature (the control will give priority to the drycooler).
Parallel control of the fans and of the variable water flow rate of 

the loop permit system operation down to -20 °C outside 

temperature without any additional control.

Pay  attention  that  drycooler  and  chiller  have  to  be  both 

equipped with the option Free Cooling Management.

NO

NC

V2V control

Chiller

DC free cooling

OAT

LEN communication

B

D

C

For an optimal free cooling operation, the chiller has to be 

configured:

• on entering water temperature control,

• on delta temperature control in case of variable speed pump 

option.

14.2.7.2 - 

Communication to control the drycooler

When  the  option  is  selected,  a  specific  electronic  board  is 

integrated in the control box of the drycooler. A communication 

LEN bus connected between the drycooler (board AUX1) and 

the chiller is needed for the overall system control.
This cable should be a 3 points Wago type (5 mm spacing or 

equivalent) and should be shielded. 
The board integrated in the control box of the drycooler has 

analog inputs for the outside air temperature (mark 1), return 

water loop temperature (mark 3) and drycooler outlet temperature 

sensors (mark 2), as well as digital outputs to control the fans.
The option works as a system split in two parts:

Chiller (with free cooling option):

 

-

Dedicated control algorithms with LEN connector to 

communicate and control the drycooler.

Drycooler (with free cooling option):

 

-

AUX board with the I/O,

 

-

OAT sensor  to be placed outside,

 

-

Dry Cooler Leaving Water Temperature (factory mounted), 

 

-

Water loop Temperature (to be mounted on the common pipe 

before valve), 

 

-

Control & 230V power supply for 2 two ways valve or one 

three ways valve

The temperature difference between dry-cooler OAT and water 

loop sensor defines if free cooling mode can be activated.

14.2.7.3 - 

Configuration of the fans control

To set the configuration corresponding to the drycooler installed 

(number of fans, control type – fixed or variable speed), please 

refer to the instructions in the TouchPilot control IOM. Following 

these parameters, the TouchPilot control will activate the 

adequate number of digital outputs to control the fans.
TouchPilot controls the automatic switching of all fans, based on 

operating time and number of start-up, to ensure a long operating 

life of fan motors.
Compatible fans configuration:

• 1 to 20 fans,

• fixed speed or variable speed

• fans on 1 or 2 lines

Refer to the drycooler electrical diagram to see the fan stages 

arrangement.

14.2.7.4 - Water valves

The free cooling system requires 2 two-way valves (one Normally 

Opened, one Normally Closed) or a three-way valve, not supplied 

with the unit or the dry cooler. 
A two-way valves kit is available in the list of drycooler 

accessories.
The drycooler electrical box includes a 230V power supply for 2 

two-way valves.
Recommended motor valve (per default): 230V 3 points
Refer to drycooler electrical diagram for valves wiring on 

customer connections.

14.2.7.5 - 

System installations recommendation

For physical characteristics, dimensions, performances: refer to 

the drycooler documentation.
For electrical connections information, refer to the electrical wiring 

delivered with the drycooler.
For  software  configuration  information,  refer  to  the  control 

documentation of the chiller.
For a proper drycooler installation, follow the professional 

guidelines for the following topics:

 

-

Water pipe sizing

 

-

pPressure drops (verify that the available pressure of the unit 

pump is sufficient compared to the piping and valves pressure 

drops - check for all running modes) ;  

 

-

Maximum drycooler elevation (in relation to the unit safety 

valve) 

 

-

Good positioning for temperature sensors: outside air 

temperature and water loop temperature..

14 - OPTIONS ET ACCESSORIES

 

 EN-59  

Dynaciat LG/LGN 

Содержание DYNACIAT LG 080

Страница 1: ...DYNACIAT LG LGN 07 2018 10188 Instruction manual...

Страница 2: ...Dynaciat LG LGN EN 2...

Страница 3: ...EN 3 Dynaciat LG LGN...

Страница 4: ...26 4 4 Electrical data optional hydraulic module 27 4 5 Compressor usage and electrical data table 30 5 APPLICATION DATA 32 5 1 Operating limits 32 5 2 Operating range 33 5 3 Minimum chilled water flo...

Страница 5: ...er pump suction filter 53 13 11 External temperature sensor 53 14 OPTIONS ET ACCESSORIES 54 14 1 Options table 54 14 2 Description 55 15 MAINTENANCE 60 15 1 Soldering and welding 60 15 2 General syste...

Страница 6: ...include the fuse plugs and safety valves if used in the refrigerant or heat transfer medium circuits Check if the original protection plugs are still present at the valve outlets These plugs are gene...

Страница 7: ...and the installation All welding operations must be carried out by qualified specialists Any manipulation opening or closing of a shut off valve must be carried out by a qualified and authorised engi...

Страница 8: ...s and possible rupture discs Be ready to switch off the main disconnect switch of the power supply if the pressure switch does not trigger avoid over pressure or excess gas in case of valves on the hi...

Страница 9: ...esignated for their recovery Do not incinerate Do not attempt to remove refrigerant circuit components or fittings while the machine is under pressure or while it is running Be sure pressure is at 0 k...

Страница 10: ...hey do not require earthquake resistance Earthquake resistance has not been verified In case of extra high units the machine environment must permit easy access for maintenance operations Only use sli...

Страница 11: ...gements provided by the manufacturer to comply with the regulations are in place Verify that all documents for pressure containers certificates name plates files instruction manuals provided by the ma...

Страница 12: ...awings Refer to the certified dimensional drawings provided with the unit or available on request when designing an installation Legend All dimensions are given in mm B Evaporator C Condenser D Safety...

Страница 13: ...to the certified dimensional drawings provided with the unit or available on request when designing an installation Legend All dimensions are given in mm B Evaporator C Condenser D Safety relief valve...

Страница 14: ...4 1488 HT 901 204 450 192 461 315 247 321 238 900 700 700 700 a g a f o m m m m NOTE Non contractual drawings Refer to the certified dimensional drawings provided with the unit or available on request...

Страница 15: ...0 700 700 884 897 f o m m a m m a g EXTERNAL DISCONNECT SWITCH NOTE Non contractual drawings Refer to the certified dimensional drawings provided with the unit or available on request when designing a...

Страница 16: ...awings Refer to the certified dimensional drawings provided with the unit or available on request when designing an installation Legend All dimensions are given in mm B Evaporator C Condenser D Safety...

Страница 17: ...rawings Refer to the certified dimensional drawings provided with the unit or available on request when designing an installation Legend All dimensions are given in mm B Evaporator C Condenser D Safet...

Страница 18: ...700 880 321 238 1021 653 192 204 247 558 1463 893 m m m m a g f o a EXTERNAL DISCONNECT SWITCH NOTE Non contractual drawings Refer to the certified dimensional drawings provided with the unit or avai...

Страница 19: ...m m 731 255 312 335 51 720 282 1574 897 884 900 700 2339 2381 HT 700 700 EXTERNAL DISCONNECT SWITCH NOTE Non contractual drawings Refer to the certified dimensional drawings provided with the unit or...

Страница 20: ...3 6 4 2 4 6 5 8 4 9 2 9 6 10 4 12 5 Max water side operating pressure without hydraulic module kPa 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 Condenser Plate heat exchanger Water volume l...

Страница 21: ...module kPa 1000 1000 1000 1000 1000 1000 Condenser Plate heat exchanger Water volume l 15 18 17 35 19 04 23 16 26 52 29 05 Max water side operating pressure without hydraulic module kPa 1000 1000 100...

Страница 22: ...ithout hydraulic module kPa 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 Hydraulic module optional Single pump as required Pump victaulic screen filter purge valves water and air pressure se...

Страница 23: ...reen filter drain valves water and air pressure sensors Expansion tank volume l 25 25 25 35 35 35 Expansion vessel pressure 4 bar 4 4 4 4 4 4 Max water side operating pressure with hydraulic module kP...

Страница 24: ...air temperature 35 C 4 Unit maximum current at 400 V in non continuous operation indicated on the unit name plate 5 Unit maximum current at 360 V in non continuous operation LG 360 600 electrical data...

Страница 25: ...outlet 12 C 7 C outdoor air temperature 35 C 4 Unit maximum current at 400 V in non continuous operation indicated on the unit name plate 5 Unit maximum current at 360 V in non continuous operation L...

Страница 26: ...2 NSX 100N DYNACIAT LG LGN 360 390 450 480 520 600 Value with upstream protection Short time 1s assigned current Icw kA rms 5 5 5 5 5 5 5 5 5 5 5 5 Allowable peak assigned current lpk kA pk 20 20 20...

Страница 27: ...ACIAT LG LGN evaporator with variable or fixed speed low pressure hydraulic module and single pump option motors N 2 Description 3 DYNACIAT LG LGN 360 390 450 480 520 600 1 Nominal efficiency at full...

Страница 28: ...2 81 2 81 2 81 2 81 2 81 2 82 2 82 2 82 2 82 2 82 2 Nominal efficiency at 50 rated load and nominal voltage 78 3 78 3 78 3 78 3 78 3 78 3 79 0 79 0 79 0 79 0 79 0 2 Efficiency level IE3 IE3 IE3 IE3 IE...

Страница 29: ...87 10 87 10 87 10 88 10 88 10 Nominal efficiency at 75 rated load and nominal voltage 84 60 84 60 84 60 84 60 87 50 87 50 Nominal efficiency at 50 rated load and nominal voltage 82 50 82 50 82 50 82...

Страница 30: ...to the operating conditions given in this manual or in the specific conditions in the manufacturer selection programs IV Potentially explosive atmospheres Non ATEX environment 1 Additional electrical...

Страница 31: ...e humidity at 20 C altitude 2000 m see note for table 4 5 in the IOM indoor installation presence of water class AD2 possibility of water droplets presence of hard solids class 4S2 no significant dust...

Страница 32: ...LG unit operating limits drycooler LG drycooler Minimum Maximum Water type heat exchanger Evaporator Water inlet temperature at start up C 7 5 1 27 Water outlet temperature in operation C 5 2 20 Inle...

Страница 33: ...r be less than 2 5 K lower than the chilled water entering temperature 5 4 Maximum chilled water flow The maximum chilled water flow is limited by the maximum permitted pressure drop in the evaporator...

Страница 34: ...7 3 7 5 8 1 Maximum flow rate for a pressure drop of 100 kPa in the water exchanger 2 Maximum flow rate for an available pressure of 20 kPa unit with low pressure pumps or 50 kPa high pressure Water t...

Страница 35: ...50 75 340 225 115 1180 655 281 1376 918 393 10 EG l 165 110 53 255 170 85 896 498 213 1045 697 299 20 EG l 100 70 35 150 100 50 741 412 176 864 576 247 35 EG l 85 55 30 130 85 45 638 354 152 744 496 2...

Страница 36: ...16 11 14 12 11 360 14 480 12 390 15 520 13 450 16 600 DYNACIAT LG condenser Sizes 080 150 Pressure drop kPa Water flow rate l s 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 0 0 0 5 1 0 1 5 2...

Страница 37: ...from the 400 V average AB 406 400 6 BC 400 399 1 CA 400 394 6 The maximum deviation from the average is 6 V The greatest percentage deviation is 100 x 6 400 1 5 This is less than the permissible 2 an...

Страница 38: ...drop 5 Cable type mm per phase mm per phase m mm per phase m 080 1 x 35 1 x 2 5 60 PVC Cu 1 x 4 100 PVC Cu 090 1 x 35 1 x 2 5 60 PVC Cu 1 x 4 100 PVC Cu 100 1 x 35 1 x 4 80 PVC Cu 1 x 6 120 PVC Cu 12...

Страница 39: ...ntrol box and the NRCP master board of the Dynaciat LG unit Configuration in Pro Dialog the number of fan stages and fan type based on the air cooled condenser used in the installation Use of a variab...

Страница 40: ...he system increase in absorbed power and decrease in cooling capacity Increasing the diameter of pipes limits pressure drops Pressure drops in the liquid pipe joining the condenser outlet to the expan...

Страница 41: ...1 5 8 1 3 8 1 3 8 1 3 8 60 70 m inch 1 3 8 1 5 8 1 5 8 1 5 8 1 5 8 1 5 8 1 5 8 1 5 8 70 m or more inch 1 3 8 1 5 8 1 5 8 1 5 8 1 5 8 1 5 8 1 5 8 1 5 8 Recommended diameters to ensure oil return within...

Страница 42: ...Sizing the liquid pipe The LGN unit compressors are provided charged with completely miscible oil with R410A refrigerant in the liquid phase As a result low refrigerant speeds inside the liquid pipe...

Страница 43: ...ify that the water circuits are connected to the appropriate heat exchangers e g no reversal between evaporator and condenser Do not introduce any significant static or dynamic pressure into the heat...

Страница 44: ...valve optional hydraulic safety components on evaporator and condenser side 4 Water pump 5 Air bleed valve 6 Water drain valve 7 8 Pressure sensor inlet outlet 9 10Temperature sensor inlet outlet 11...

Страница 45: ...unit and hydraulic module 1 Compressor 2 Condenser 3 Expansion device 4 Evaporator 5 Temperature sensor inlet outlet 6 Water drain valve 7 Flow rate switch 8 Flexible connection coupling Option 09 10...

Страница 46: ...it and as a safety precaution add ethylene glycol to the heat exchanger using the heat exchanger water entering purge valve connection At the start of the next season refill the unit with water and ad...

Страница 47: ...r to the controls manual and let the pump run for two consecutive hours to clean the hydraulic circuit of the system presence of solid contaminants Read the hydraulic module pressure drop by taking th...

Страница 48: ...ger pressure drop to be measured with the pressure gauge installed at the water inlet and outlet 3 Installation pressure drop with control valve wide open 4 Installation pressure drop after valve cont...

Страница 49: ...Pressure head kPa Water flow rate l s 7 LG LGN 180 8 LG LGN 200 9 LG LGN 240 10 LG LGN 260 11 LG LGN 300 Sizes 360 600 30 0 40 0 50 0 60 0 70 0 80 0 90 0 100 0 110 0 120 0 130 0 140 0 150 0 160 0 170...

Страница 50: ...90 100 110 120 130 140 150 160 170 180 190 200 210 220 0 1 2 3 4 5 6 7 8 9 10 11 12 13 12 17 Water flow rate l s 12 LG LGN 360 13 LG LGN 390 14 LG LGN 450 15 LG LGN 480 16 LG LGN 520 17 LG LGN 600 Dyn...

Страница 51: ...ct Touch control manual The compressors cannot support prolonged operation 30 seconds with reversed phases Ensure that the last refrigerant charge made by the service team corresponds with the charge...

Страница 52: ...quick connect Victaulic couplings to facilitate pump disassembly if required A drain with a 1 4 turn valve is included in the leaving water of all heat exchangers The evaporators have 19 mm thick pol...

Страница 53: ...ure indicator shows when it is necessary to change the filter cartridges A temperature difference between the filter drier inlet and outlet indicates a contamination of the cartridges LGN units are de...

Страница 54: ...e Easy and fast installation plug play significant pumping energy cost savings more than two thirds tighter water flow control improved system reliability Lon gateway Bi directional communication boar...

Страница 55: ...External temperature sensor External temperature sensor control for using weather compensation Allow to adjust set point using weather compensation and define authorisation operation mode to external...

Страница 56: ...tions available These assembly examples apply to the evaporator side It s the same assembly on the condenser side Screen filter evaporator option Flexible piping hydraulic Customer screwed connection...

Страница 57: ...ages up to 8 stages maximum and of the variable water flow rate of the loop permit year round system operation down to outside temperatures of 10 C without any additional control 14 2 5 2 Communicatio...

Страница 58: ...ble speed fan variants 14 2 6 2 Lead fan The physical position of the air cooled condenser with fixed or variable speed fans depends on the position of the leaving liquid refrigerant manifold In all c...

Страница 59: ...and control the drycooler Drycooler with free cooling option AUX board with the I O OAT sensor to be placed outside Dry Cooler Leaving Water Temperature factory mounted Water loop Temperature to be mo...

Страница 60: ...ndition Regularly check that the vibration levels remain acceptable and close to those at the start of using the unit For units equipped with pump regularly check that no leak appears on the pump High...

Страница 61: ...pressure temperature ratio table must be used to determine the corresponding saturated temperatures saturated bubble point curve or saturated dew point curve Leak detection is especially important fo...

Страница 62: ...ers must always be within the compressor operating range Check that the safety devices are all operational and correctly controlled Check oil level and quality If there is a colour change in the sight...

Страница 63: ...artridges after carrying out a leak test of the circuit Electrical checks Check the tightening of the electric connections contactors disconnect switch and transformer Check the phase direction upstre...

Страница 64: ...can be recycled for another purpose 17 3 Fluids to be recovered for treatment Refrigerant Energy transfer fluid depending on the installation water glycol water mix Compressor oil 17 4 Materials to be...

Страница 65: ...circuit protection has been sized and installed properly All terminals are tight All cables and thermistors have been inspected for crossed wires All plug assemblies are tight Check air handling syste...

Страница 66: ...lay for any alarms such as phase reversal Follow the TEST function instructions in the Controls and Troubleshooting literature follow the procedure in the Controls IOM Be sure that all service valves...

Страница 67: ...EN 67 Dynaciat LG LGN...

Страница 68: ...ie Industrielle d Applications Thermiques S A au capital de 26 728 480 R C S Bourg en Bresse B 545 620 114 Non contractual document With the thought of material improvement always in mind CIAT reserve...

Отзывы: