4 - PHYSICAL AND ELECTRICAL DATA
D YNACIAT LG/LGN condenser with variable speed double high pressure hydraulic module and single pump option motors
No.
(2)
Description (3)
DYNACIAT LG
360
390
450
480
520
600
1
Nominal efficiency at full load and nominal voltage
%
87,10
87,10
87,10
88,10
88,10
88,10
Nominal efficiency at 75% rated load and nominal voltage
%
84,60
84,60
84,60
87,50
87,50
87,50
Nominal efficiency at 50% rated load and nominal voltage
%
82,50
82,50
82,50
86,50
86,5
86,5
2
Efficiency level
%
IE3
IE3
IE3
IE3
IE3
IE3
3
Year of manufacture
This information varies depending on the manufacturer and model at the
time of incorporation. Please refer to the motor name plates.
4
Manufacturer's name and trademark, commercial registration number and place of
manufacturer
5
Product's model number
6
Number of motor poles
2
2
2
2
2
2
7-1
Nominal shaft power output at full load and nominal voltage (400 V)
kW
3
3
3
4
4
4
7-2
Maximum input power (400 V)(4)
kW
3,44
3,44
3,44
4,54
4,54
4,54
8
Rated input frequency
Hz
50
50
50
50
50
50
9-1
Nominal voltage
V
400V 3P
400V 3P
400V 3P
400V 3P
400V 3P
400V 3P
9-2
Maximum current drawn (400 V)(5)
A
6,15
6,15
6,15
7,84
7,84
7,84
10
Rated speed
rpm
2915
2915
2915
2930
2930
2930
r/s
48,58
48,58
48,58
48,83
48,83
48,83
11
Product disassembly, recycling or disposal at end of life
Disassembly using standard tools. Disposal and recycling using an
appropriate company.
12
Operating conditions for which the motor is specifically designed
I - Altitudes above sea level
m
< 1000(6)
II - Ambient air temperature
°C
< 40
III - Maximum operating temperature
°C
Please refer to the operating conditions given in this manual or in the
specific conditions in the manufacturer selection programs.
IV - Potentially explosive atmospheres
Non-ATEX environment
(1) Additional electrical data required by regulation No. 640/2009 concerning the application of directive 2009/125/EC on the eco-design requirements for electric
motors.
(2) Item number imposed by regulation No. 640/2009, annex I2b.
(3) Description given by regulation No. 640/2009, annex I2b.
(4) To obtain the maximum input power for a unit with hydraulic module, add the "maximum unit input power" from the electrical data table to the pump power.
(5) To obtain the maximum unit operating current draw for a unit with hydraulic module add the "maximum unit current draw" from the electrical data table to the pump
current draw.
(6) Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration.
4.5 - Compressor usage and electrical data table
LG
Compressor
I Nom
I Max (Un)
I Max (Un - 10%)
LRA
(1)
LRA
(2)
Cos Phi Max
WSH090
10,5
15,6
17,3
98
53,9
0,85
WSH105
13,2
18,7
20,8
142
78,1
0,85
WSH120
13,8
19,8
22
142
78,1
0,85
WSH140
15,6
23,2
25,8
147
80,9
0,87
WSH161
16,2
25,4
28,2
158
86,9
0,85
WSH184
20,2
29
32,2
197
108,4
0,85
LGN
Compressor
I Nom
I Max (Un)
I Max (Un - 10%)
LRA
(1)
LRA
(2)
Cos Phi Max
WSH090
11,4
15,6
17,3
98
53,9
0,85
WSH105
13,8
18,7
20,8
142
78,1
0,85
WSH120
14,7
19,8
22
142
78,1
0,85
WSH140
16,5
23,2
25,8
147
80,9
0,87
WSH161
18,1
25,4
28,2
158
86,9
0,85
WSH184
21,2
29
32,2
197
108,4
0,85
Legend
I Nom
Nominal current draw (A) at standard Eurovent conditions see definition of conditions under nominal unit current draw)
I Max
Maximum operating current, A
LRA
(1)
Locked rotor current at nominal voltage, A
LRA
(2)
Locked rotor current with electronic starter at nominal voltage, A
Dynaciat LG/LGN
EN-30