EN
EN - 35
EN7510364-00
No.
PARAMETER NAME
PARAMETER ADJUSTMENT
Notes
Description
Display conditions
Adjustment
possible
By
default
Adjustment
conditions
A120
No. of SETPOINTS
1 setpoint
2 per console or CMS
1
A121
SETPOINT 1
A02 = 1 and A03 = 1
5 to 90
60
A03 = 1 or 2 LT
SETPOINT 1, COIL 1
A02 = 2 and A03 = 1
5 to 150
120
A03 = 1 or 2 HT
SETPOINT 1, CIRCUIT 1
A02 = 1 and A03 = 2
5 to 45 b
(increments of 0.5)
12
A03 = 1 or 2 refrig.
STP1 COIL 1 CIRCUIT 1
A02 = 2 and A03 = 2
A122
SETPOINT 2
A02 = 1 and A03 = 1 and
A120 = 2
5 to 90
50
A03 = 1 or 2 LT
SETPOINT 2, COIL 1
A02 = 2 and A03 = 1 and
A120 = 2 or 3
5 to 150
100
A03 = 1 or 2 HT
SETPOINT 2, CIRCUIT 1
A02 = 1 and A03 = 2 and
A120 = 2 or 3
5 to 45 b
(increments of 0.5)
12
A03 = 1 or 2 refrig.
STP2 COIL 1 CIRCUIT 1
A02 = 2 and A03 = 2 and
A120 = 2 or 3
A123
SETPOINT 1, CIRCUIT 2
A02 = 1 and A03 = 2
5 to 90
60
A03 = 2 LT
STP1 COIL 1 CIRCUIT 2
A02 = 2 and A03 = 2
5 to 150
120
A03 = 2 HT
5 to 45 b
(increments of 0.5)
12
A03 = 2 refrig
A124
SETPOINT 2, CIRCUIT 2
A02 = 1 and A03 = 2 and
A120 = 2 or 3
5 to 90
50
A03 = 2 LT
STP2 COIL 1 CIRCUIT 2
A02 = 2 and A03 = 2 and
A120 = 2 or 3
5 to 150
100
A03 = 2 HT
5 to 45 b
(increments of 0.5)
12
A03 = 2 refrig
A125
SETPOINT 1, COIL 2
A02 = 2 and A05 = 1
5 to 90
60
A05 = 1 or 2 LT
STP1 COIL 2 CIRCUIT 1
A02 = 2 and A05 = 2
5 to 150
120
A05 = 1 or 2 HT
5 to 45 b
(increments of 0.5)
12
A05 = 1 or 2 refrig.
A126
SETPOINT 2, COIL 2
A02 = 2 and A05 = 1 and
A120 = 2 or 3
5 to 90
50
A05 = 1 or 2 LT
STP2 COIL 2 CIRCUIT 1
A02 = 2 and A05 = 2 and
A120 = 2 or 3
5 to 150
100
A05 = 1 or 2 HT
5 to 45 b
(increments of 0.5)
12
A05 = 1 or 2 refrig.
A127
STP1 COIL 2 CIRCUIT 2
A02 = 2 and A05 = 2
5 to 90
60
A05 = 2 LT
5 to 150
120
A05 = 2 HT
5 to 45 b
(increments of 0.5)
12
A05 = 2 refrig
A128
STP2 COIL 2 CIRCUIT 2
A02 = 2 and A05 = 2 and
A120 = 2 or 3
5 to 90
50
A05 = 2 LT
5 to 150
100
A05 = 2 HT
5 to 45 b
(increments of 0.5)
12
A05 = 2 refrig
A129
PERMANENT FAULT
5 faults in 1 hour
5 Faults
in 1 Hour
From version V07
A150
STAGE 1 HYSTERESIS
A02 = 1 and A03 = 1
1 to 20°C
(increments of 0.5)
5
If A03 = 1 or 2
water circuits
HYST. STAGE 1 COIL 1
A02 = 2 and A03 = 1
HYST. STAGE 1 CIRCUIT 1
A02 = 1 and A03 = 2
2 to 6 bar (0.5
increments)
3.5
If A03 = 1 or 2
refrig. circuit
HYST. STAGE 1 COIL.1 CIR.1
A02 = 2 and A03 = 2
A151
STAGE 2 DIFFERENCE
A02 = 1 and A03 = 1 and A08 ≥ 2
1 to 5°C
(increments of 1)
2
If A03 = 1 or 2
water circuits
STAGE 2 COIL 1 DIFFERENCE
A02 = 2 and A03 = 1 and A08 ≥ 2
STAGE 2 CIRCUIT 1 DIFFERENCE
A02 = 1 and A03 = 2 and A08 ≥ 2
0.5 to 3 bar
(increments of 0.5)
0.5
If A03 = 1 or 2
refrig. circuits
HYST. STAGE 2 COIL.1 CIR.1
A02 = 2 and A03 = 2 and A08 ≥ 2
A152
STAGE 2 HYSTERESIS
A02 = 1 and A03 = 1 and A08 ≥ 2
1 to 10°C
(increments of 0.5)
5
If A03 = 1 or 2
water circuits
HYST. STAGE 2 COIL 1
A02 = 2 and A03 = 1 and A08 ≥ 2
HYST. STAGE 2 CIRCUIT 1
A02 = 1 and A03 = 2 and A08 ≥ 2
2 to 6 bar (0.5
increments)
3.5
If A03 = 1 or 2
refrig. circuits
HYST. STAGE 2 COIL.1 CIR.1
A02 = 2 and A03 = 2 and A08 ≥ 2