EN7510364-00
EN - 28
9.4 Remote alarm register (read-only)
Register 10:
FAN FAULTS (1 = active fault)
Bit
Bit
0
Fan fault, stage 1, line 1
8
Fan fault, stage 1, line 2
1
Fan fault, stage 2, line 1
9
Fan fault, stage 2, line 2
2
Fan fault, stage 3, line 1
10
Fan fault, stage 3, line 2
3
Fan fault, stage 4, line 1
11
Fan fault, stage 4, line 2
4
Fan fault, stage 5, line 1
12
Fan fault, stage 5, line 2
5
Fan fault, stage 6, line 1
13
Fan fault, stage 6, line 2
6
Fan fault, stage 7, line 1
14
N.U.
7
N.U.
15
N.U.
Register 11
: SENSOR FAULT (1 = active fault)
Bit
Bit
0
Pressure or temperature sensor fault, coil 1, circuit 1
8
Pressure or temperature sensor fault, coil 2, circuit 1
1
Pressure or temperature sensor fault, coil 1, circuit 2
9
Pressure or temperature sensor fault, coil 2, circuit 2
2
N.U.
10
N.U.
3
N.U.
11
N.U.
4
N.U.
12
N.U.
5
N.U.
13
N.U.
6
N.U.
14
N.U.
7
N.U.
15
N.U.
9.5 Remote measurement register (read-only)
Register
Float type
Register
Float type
100 and 101
Setpoint and control coil 1, circuit 1
116 and 117
Outdoor temperature
102 and 103
Control setpoint, coil 1, circuit 2
118 and 119
Voltage between phase 1 and 2
104 and 105
Control setpoint, coil 2, circuit 1
120 and 121
Voltage between phase 2 and 3
106 and 107
Control setpoint, coil 2, circuit 2
122 and 123
Voltage between phase 1 and 3
108 and 109
Temperature or pressure, coil 1, circuit 1
124 and 125
A471 Input current
110 and 111
Temperature or pressure, coil 1, circuit 2
126 and 127
A472 Instantaneous power consumed
112 and 113
Temperature or pressure, coil 2, circuit 1
128 and 129
Total energy consumed kW/h (write 0 to reset the value)
114 and 115
Temperature or pressure, coil 2, circuit 2
9.6 Fault memory
Register 200
:
Fault memory 9
Register 201
:
Fault memory 8
Register 202
:
Fault memory 7
Register 203
:
Fault memory 6
Register 204
:
Fault memory 5
Register 205
:
Fault memory 4
Register 206
:
Fault memory 3
Register 207
:
Fault memory 2
Register 208
:
Fault memory 1
0:
Fault memory empty
0x010:
Fan fault, stage 1, line 1
0x011:
Fan fault, stage 2, line 1
0x012:
Fan fault, stage 3, line 1
0x013:
Fan fault, stage 4, line 1
0x014:
Fan fault, stage 5, line 1
0x015:
Fan fault, stage 6, line 1
0x016:
Fan fault, stage 1, line 2
0x017:
Fan fault, stage 2, line 2
0x018:
Fan fault, stage 3, line 2
0x019:
Fan fault, stage 4, line 2
0x01A:
Fan fault, stage 5, line 2
0x01B:
Fan fault, stage 6, line 2
0x01C:
Outdoor temperature sensor fault
0x01D:
Fan fault, stage 7, line 1
0x080:
Temperature sensor fault, coil 1, circuit 1
0x081:
Temperature sensor fault, coil 1, circuit 2
0x082:
Temperature sensor fault, coil 2, circuit 1
0x083:
Temperature sensor fault, coil 2, circuit 2
0x084:
Pressure sensor fault, coil 1, circuit 1
0x085:
Pressure sensor fault, coil 1, circuit 2
0x086:
Pressure sensor fault, coil 2, circuit 1
0x087:
Pressure sensor fault, coil 2, circuit 2