CIAT AeroCONNECT 1B Скачать руководство пользователя страница 24

 

EN7510364-00

 

 EN - 22 

7.3 Information available while the unit is running

In the [2-Machine status]

 menu: menu displayed on the screen if the control console is not used for one hour.

Default

Information

No faults

Setpoint and measurement values displayed.

Sensor fault

The fault LED flashes and a message indicates that the sensor has a fault

Fan fault

The stage fault LED flashes and a message indicates which stage has a fault

In the [3-Measured values] menu:

Parameter

Description 

Display conditions 

Outdoor temperature

Value displayed 

Free cooling or misting or warming function

Coil temperature 

Value displayed 

V-type or 1-coil unit/flatbed unit

Coil 1 temperature

Value displayed 

2 coils/flatbed unit

Coil 2 temperature

Value displayed 

2 coils/flatbed unit

In the [6-Reading parameters] menu: 

Parameter No.

Description

Display conditions

A250

LED test: press Enter to check the operation of 
the LEDs

A252

Outdoor air temperature 

Free cooling or misting

A253

Value of coil 1 setpoint

A255

Value of coil 2 setpoint

2 coils/flatbed unit

A257

Value of coil 1 temperature

A261

Value of coil 2 temperature

2 coils/flatbed unit

A270  to A276

Running time of each stage

A299

Misting time

Misting

A300

Free cooling time

Free cooling

A316

Terminal block J9 connection

From V09

A400 to 421

Status (open or closed) of the logic inputs on the 
board

A430 to A451

Status (open or closed) of the logic outputs on the 
board

A460

Fan speed in%

Control = mixed or speed control

From V07

A470

Supply voltage 

Energy meter

A471

Machine input current

Energy meter 

A472

Machine power input 

Energy meter 

A473

Electrical energy consumed

Energy meter

A555

CPU board version No.

A556

Control console version No.

A557

Daughter board version No.

In the [7 - Fault memory] menu:

Record of the nine most recent faults on the fan stages or temperature sensors. To scroll through the faults, press 

Содержание AeroCONNECT 1B

Страница 1: ...AEROCONNECT 1B 01 2017 EN7510364 00 C o n t r o l m a n u a l...

Страница 2: ......

Страница 3: ...enu 11 14 4 10 Link with a CIAT chiller 14 5 OPTIONS 15 5 1 Energy meter From V07 15 5 2 Relay boards 15 5 3 Remote control console 15 6 ELECTRICAL CONNECTIONS 16 6 1 Connection diagram 16 6 2 Board c...

Страница 4: ...it must be earthed using an official earthing system which complies with French standard C15 100 1 5 Sensor connections Do not pass connection cables near to a power line 400 V or remote control line...

Страница 5: ...abel found on the board 2 3 Usage limitations Room air chap 1 2 Single phase fluid min max adjustment temperature 5 90 C up to 150 C optional Refrigerant fluid min max set pressure 5 45 bar 2 4 Electr...

Страница 6: ...n off button B LED on system powered on C Fan fault acknowledgment D LED on fault E Press this button to select setpoint 1 or 2 The LEDs show the active setpoint F Display screen G Menu navigation but...

Страница 7: ...ings parameters Configuration of the control and various options 6 Reading parameters Displays the state of the inputs outputs meters etc read only 7 Fault memory Shows the nine most recent faults rea...

Страница 8: ...e display to scroll faster Powered on The machine stopped on off menu 2 Machine state screen appears Press to go back to the menu list If the console is not used for one hour the 2 Machine state menu...

Страница 9: ...152 A154 A156 A158 A160 A159 A157 A155 A151 A153 1 A150 EXAMPLE FOR CIRCUIT 1 A121 or A122 Setpoint Measurement Stage no 2 Stage no 3 Stage no 4 Stage no 5 Stage no 6 Stage 6 hysteresis Stage 5 hyster...

Страница 10: ...ine units and or 2 circuit units Stage operation Stage control is defined according to a percentage of the operating range of the 1st stage 7 stages 5 15 25 30 40 45 and 50 55 65 75 85 95 6 stages 5 1...

Страница 11: ...e continues to rise for A107 regulation put into operation an additional control stage If the fluid temperature A121 A106 and when the temperature continues to drop for a period A108 the control cut a...

Страница 12: ...the value of parameter A113 Optimised water consumption A113 WATER the water misting does not start until all the stages are on Optimised electricity consumption A113 ELEC the water misting does not c...

Страница 13: ...the fan output signal is equal to 6V With variable speed control From version V07 it is possible to activate misting before being at 100 on the drycooler by modifying the value of parameter A113 1 A 1...

Страница 14: ...horisation to the water chiller The water chiller controls according to its own parameters This authorisation is timed for 15 minutes when the drycooler is started 4 7 3 Electrical connections ADD2 bo...

Страница 15: ...tion This function is available for drycoolers with 1 coil and 1 circuit from version V07 It is activated by selecting the parameter A109 A 1 0 9 O P E R A T I O N O F C O O L I N G W A R M I N G W I...

Страница 16: ...hiller to J9 of the drycooler for drycooler software versions V09 2 Configure the following parameters P116 of water chiller YES A116 of drycooler YES for software versions V09 On software versions V0...

Страница 17: ...the drycooler board parameters are accessible in read and write mode 1 3 A E R O C O N N E C T Menu 13 displays all the drycooler data on the water chiller console The drycooler parameters are prefixe...

Страница 18: ...J11 borne 3 J11 borne 1 J11 borne 2 J11 borne 3 J12 UNIT NO 1 Local console UNIT NO 2 UNIT NO X 1 Local console UNIT NO X RS485 2 wires Max length 1000m Controller or PC output RS485 Position of line...

Страница 19: ...1 4 3 2 1 4 3 2 1 8 6 4 2 7 5 3 1 1 1 2 3 4 5 1 2 3 Shared Shared 6 2 Board connections 6 2 1 Motherboard The structure of the motherboard is illustrated in the diagram below 1 2 3 4 1 2 3 J9 J12 W3 3...

Страница 20: ...ECT board terminal 1 to terminal 1 terminal 2 to terminal 2 and shielding to terminals 3 or customer CMS Its potential free dry contacts allow the following information to be viewed remotely CONNECTOR...

Страница 21: ...minals 1 3 Fan fault stage 1 line 2 J9 terms 1 4 Fan fault stage 2 line 2 J9 terms 5 6 Fan fault stage 3 line 2 J9 terms 5 7 Fan fault stage 4 line 2 J9 terms 5 8 Fan fault stage 5 line 2 J10 terminal...

Страница 22: ...Default values Display conditions Menu 5 Settings parameters A100 Language EN A103 Console control type local A104 Communication mode baud 9600 CMS A105 Bus number 1 CMS From V07 A106 Range without f...

Страница 23: ...0 C 5 C V type or 1 coil unit flatbed unit Hysteresis stage 1 coil 1 1 to 20 C 2 coils flatbed unit A151 Difference between stages 1 and 2 1 to 5 C 2 C Control On Off No of stages 2 V type or 1 coil u...

Страница 24: ...conditions A250 LED test press Enter to check the operation of the LEDs A252 Outdoor air temperature Free cooling or misting A253 Value of coil 1 setpoint A255 Value of coil 2 setpoint 2 coils flatbe...

Страница 25: ...er other than those that require changing and relock them Parameter No Parameter description Display condition A01 Unit type flatbed or V coil A02 Number of coils 1 or 2 Flatbed unit Parallel coil yes...

Страница 26: ...unit or A124 A126 Setpoint 2 circuit 2 12 bar 2 setpoints 2 refrig circ flatbed unit Setpoint 2 coil 2 2 setpoints V type unit From V07 A129 Permanent fault 5 in 1 hour A150 Stage 1 hysteresis circui...

Страница 27: ...2 setpoint V type unit A258 Value of circuit or coil 1 pressure A260 Value of circuit 2 pressure 2 refrig circuits flatbed unit A262 Value of coil 2 pressure V type unit A270 to A276 Running time of e...

Страница 28: ...ff or mixed A09 Number of fan lines 1 or 2 Flatbed unit 2 refrigerant circuits A10 Misting yes or no From V07 A15 1 Measurement of electrical quantities A15 2 NET electrical network type A15 1 YES A16...

Страница 29: ...ics counters 11 read event counter 15 write n bits 16 write multiple registers 16 bits Note functions 15 and 16 are possible if parameter A706 is set to Remote CMS Error codes 1 unknown function code...

Страница 30: ...8 and 109 Temperature or pressure coil 1 circuit 1 124 and 125 A471 Input current 110 and 111 Temperature or pressure coil 1 circuit 2 126 and 127 A472 Instantaneous power consumed 112 and 113 Tempera...

Страница 31: ...0 1 low temperature water circuit 1 2 low temperature water circuits 2 1 high temperature water circuit 3 2 high temperature water circuits 4 1 refrigerant circuit 5 2 refrigerant circuits Register 4...

Страница 32: ...A174 Hysteresis stage 2 coil 2 circuit 1 Registers 518 and 519 A175 Setpoint difference stage 3 coil 2 circuit 1 Registers 520 and 521 A176 Hysteresis stage 3 coil 2 circuit 1 Registers 522 and 523 A...

Страница 33: ...essure fault coil 2 circuit 2 Bit 17 On off 1 on on and AOC closed Bit 18 Spray state 1 on Bit 19 Free cooling state 1 on Bit 20 General fault summary Bit 21 Connection fault with the Diris module 9 9...

Страница 34: ...uit 1 Refrig circuit 2 LT water circuits 2 HT water circuits 2 refrig circuits 1 LT water circuit 1 HT water circuit 1 Refrig circuit 2 LT water circuits 2 HT water circuits 2 refrig circuits 1 LT wat...

Страница 35: ...ISTING Yes and No No A15 1 ELECTRICAL QUANTITY MEASUREMENT Yes and No No Visible if energy meter option A15 2 TYPE OF NET ELECTRICAL GRID 1BL 2BL 3BL 4BL 3NBL 4NBL 3BL A16 PRIMARY CT RATING 5 to 1000...

Страница 36: ...operation of free cooling Info for maintenance A113 MISTING A10 Yes Elec Water Water A113 1 MISTING CONTROL SIGNAL FAN A113 Water A10 YES A07 Speed control 4 to A114 in increments of 0 5V 10 From V07...

Страница 37: ...frig A126 SETPOINT 2 COIL 2 A02 2 and A05 1 and A120 2 or 3 5 to 90 50 A05 1 or 2 LT STP2 COIL 2 CIRCUIT 1 A02 2 and A05 2 and A120 2 or 3 5 to 150 100 A05 1 or 2 HT 5 to 45 b increments of 0 5 12 A05...

Страница 38: ...5 1 to 5 C increments of 1 2 If A03 1 or 2 water circuits STAGE 5 COIL 1 DIFFERENCE A02 2 and A03 1 and A08 5 STAGE 5 CIRCUIT 1 DIFFERENCE A02 1 and A03 2 and A08 5 0 5 to 3 bar increments of 0 5 0 5...

Страница 39: ...2 DIFFERENCE A02 2 and A03 2 and A08 5 0 5 to 3 bar increments of 0 5 0 5 If A03 1 or 2 refrig circuit A169 HYST STAGE 5 CIRCUIT 2 A02 1 and A03 2 and A08 5 1 to 10 C increments of 1 5 If A03 1 or 2...

Страница 40: ...ircuits 2 to 6 bar 0 5 increments 3 5 If A05 2 refrig circuit A184 STAGE 2 COIL 2 CIR 2 DIFFERENCE A02 2 and A05 2 and A08 2 1 to 5 C in increments of 1 2 If A05 2 water circuits 0 5 to 3 bar incremen...

Страница 41: ...CIR 2 DIFFERENCE A02 2 or no and A03 2 0 5 to 3 bar 0 5 increments 0 5 If A03 2 refrig circuits A202 MIST STAGE COIL 2 DIFFERENCE A02 2 or no and A05 1 1 to 5 C in increments of 1 2 If A05 1 or 2 wat...

Страница 42: ...ustrielle d Applications Thermiques Corporation with a capital of 26 728 480 R C S Bourg en Bresse B 545 620 114 With Ecofolio all papers can be recycled This document is not legally binding As part o...

Отзывы: