100 %
P 130
Valve ctrl
Heating operation
Hot Proportional Band
P152 or P153
Setpoint
Room T°
5.2.2.3 Cooling coil, COOLING mode
"Stop" position: the valve is closed
"COMFORT" position: the opening of the valve will depend on the difference between the regulated temperature value (room)
and the setpoint. Regulation will only start after a 30-second time delay on the fan operation feedback contact. An integral action
must be entered into the parameters.
0 %
100 %
P 135
Valve ctrl
Cooling operation
Cold Proportional Band
P150 or P151
Cooling setpoint
Room T°
5.3 TPL regulation:
TPLs are destratifiers which can only be regulated according to the fan speed.
This is calculated from the difference between the room temperature measured by the sensor in the Master 1-ph HEE BOX (or
remotely if this option has been chosen) and the sensor fitted in the TPLs.
EN-21