F0.01 Run command channel
Setting Range:0
~
2 Factory setting: 0
Chapter 6 Detailed function description
-87-
This function is used to set the inverter receive the control mode which forward,
reverse, jog and stop ect control command.
0: Keyboad command channel
To control the inverter start and stop by the key RUN
、
STOP
、
REV/JOG On the
keypad.
1: Terminal command channel
To control the inverter start and stop by external control terminal Xn—COM on
and off .
2: Communication command channel
To control the inverter start and stop by RS485 serial port.
F0.02 Keyboard and terminal UP/Down setting
Setting range:0
~
3 Factory setting : 0
The frequency can be set by ▲/▼ or encoder on the keypad and terminal
UP/DOWN.This setting method have the highest and it can be combined with setting
channel .It is used to adjust the output frequency during the commission of the control
system .
0
:
Valid , save the parameters when the inverter is power off .
The frequency command can be set and the value can be saved after the inverter is
powered off and it will combinate with the current frequency when it is repowered on .
1
:
Valid ,the value can not be saved when the inverter is powered off.
The frequency command can be set but the value can not be saved after the inverter
is powered off .
Содержание ZVF300H
Страница 2: ......
Страница 3: ...Software Version V3 75 Printing Date 2020 09 ZVF300H ZVF300H ...
Страница 4: ...P1 P8 P1 P2 P2 P3 P5 P8 P9 P17 P9 P9 P9 P10 P13 P15 P18 P38 P18 P19 P24 P35 P39 P42 P39 ...
Страница 6: ......
Страница 7: ......
Страница 8: ......
Страница 9: ...method ...
Страница 10: ...not personnal ...
Страница 11: ...suitable ...
Страница 12: ......
Страница 13: ...Figure 1 5 Three phase AC Power supply ...
Страница 15: ...Board ...
Страница 16: ...Board ...
Страница 17: ...3 Cabinet Body 8 The door of cabinet Board ...
Страница 21: ...150 600 50 ...
Страница 22: ......
Страница 23: ......
Страница 24: ......
Страница 25: ......
Страница 26: ......
Страница 27: ...2 ...
Страница 28: ......
Страница 31: ......
Страница 32: ......
Страница 33: ...Applicable to model ZVF300H G0R4T2 3R7T2 ZVF300H G0R7T4 7R5T4 ZVF300H P4R0T4 011T4 ZVF300H ...
Страница 41: ......
Страница 44: ...ZVF300H ZVF300H ...
Страница 45: ......
Страница 46: ......
Страница 47: ......
Страница 48: ...till ...
Страница 49: ...ZVF300H ...
Страница 50: ...AO1 ...
Страница 51: ...AO1 ...
Страница 52: ...AO1 15 ...
Страница 53: ...AO1 ...
Страница 176: ... 171 ...
Страница 177: ... 172 ...
Страница 178: ... 173 ...
Страница 179: ... 174 ...
Страница 180: ... 175 ...
Страница 181: ... 176 ...
Страница 182: ... 177 ...
Страница 183: ... 178 ...
Страница 184: ... 179 ...
Страница 185: ... 180 ...
Страница 186: ... 181 ...
Страница 191: ... 186 ...
Страница 192: ... 187 ZVF300H G132 P160T4 ...
Страница 195: ... 190 ...
Страница 196: ... 191 ...
Страница 197: ... 192 ...
Страница 198: ... 193 ...
Страница 199: ... 194 ...
Страница 200: ... 195 ...
Страница 201: ... 196 ...
Страница 202: ... 197 ...
Страница 205: ... 200 8 E 1 8 O 1 Communication data structures Communication data format box ASCII mode ...
Страница 208: ... 203 RTU mode ...
Страница 211: ... 206 ...
Страница 214: ... 209 3 6 The definition of communication of Parameter address ...
Страница 215: ... 210 Table 3 1 Table 3 2 ...
Страница 216: ... 211 Appendix Table 3 1 Data and fault type in 5000H ...
Страница 218: ... 213 Appendix Table 3 2 Data and fault type in 5001H ...
Страница 219: ... 214 ...