Chapter 4  Operation

4.1 Check before operation.

The following steps should be inspected and confirmed before the soft starter is put 
into operation:

Be sure that the application ambient and the input power supply complywith the 

requirements in this manual.

Be sure that the main circuit is properly wired: The input power supply must be 

connected to the terminals R, S and T; the output terminals U, V and W must be 
connected to the motor; the bypass electromagnetic contactor is installed and properly 
connected; the ground terminal is reliably and properly grounded.

Be sure there is no short cutting or short to ground of all terminals and electrified 

parts. All terminals, connectors and screws are tightly fastened.

  

4.2 Operation

Now start a trial operation after all the inspection steps in 4.1 have been done. While in 
trial operation, it is suggested that the motor has vacant load. If everything is OK, then 
perform on-load running.
Be careful to select an optimum mode of operation in accordance with specific 
operational requirements. See the detail below:

 The factory default setting of the product operation mode is operation panel control.
 The value of rated power current PC should be set to the same as the one on the 

motor's specifications label.

 Press          to start the motor and press           to end it. 
 Be sure the motor has a smooth running without whistler or vibration.
 If the motor starting is not good enough, just change settings of the basic functions 

of P1.

 If the motor's starting torque is not powerful enough, just change the inception 

voltage code P0 (indicating voltage mode enabled) or the current-limiting value code 
P3 (indicating current mode enabled) to raise the torque.

 Be sure the motor rotates in the correct direction.

Only after making sure there is no anomaly, can the motor be put into formal operation.

Notes: 
1) If there is any anomaly of the soft starter or the motor, or there is a display of the 
fault code 

F XX, just stop operation immediately and deal with it in accordance with 

the protective requirements in Chapter 6.
2) If the on-spot ambient temperature is lower than -10

, please restart the machine 

more than 30 minutes lather after it is energized and preheated.

Chapter 5  Description of Function Parameters

5.1 Schedule of Function Parameters

Function 
Code

Function Name

Setting Range

Default 
Value

MEMO

Inception Voltage

Period of Starting

Period of Soft Stop

Starting limitation Current

Max. Working Current

Undervoltage Protection

Overvoltage Protection

Starting Modes

Protection Classes

Control Modes

Parameter Protection

Programming Output

Motor Rated Current

Motor Protection

00: current limiting; 01: voltage 
ramp; 02: kick + current-limiting; 
03: kick + voltage ramp; 04: 
current ramp; 05: voltage and 
current-limiting double closed loop

00: primary; 01: light load; 02: 
standard; 03: heavy load; 04: 
advanced

00: operation panel control;
01: operation panel + external control;
02: external control;
03: external c COM control;
04: operation panel + ex COM 
control;
05: operation panel + COM control;
06: COM control;
07: start/stop disabled

00: parameter modification disabled;
01: parameter modification enabled

00~19 detailed in Page 24 Functional 
Code Pb

Set according to
 specifications.

Notes:
1) Idle keys for over 2 minutes, the machine will escape from the setting state 
automatically.
2) Do not set parameters during soft start or soft stop. Set them in other states.

Содержание ZJR1 Series

Страница 1: ...ZJR1 SERIES SOFTSTART USER S MANUAL...

Страница 2: ...ty Instructions 1 1 2 Product Inspection upon Arrival 2 1 3 Demonstration of the Specifications Label and Model 2 1 4 Outline of the Product 3 1 5 Models and Specifications 4 1 6 Technical Indications...

Страница 3: ...ails in the input and output ports with insulated sheath or tape When the motor soft starter is under remote control do lock the keyboard control to avoid accidence due to error operation Do cut off t...

Страница 4: ...W Nameplate Base Circuit Board Cabinet Connect to the bypass contactor L21 L22 L23 Input Terminals of Power Supply R S T Operation Panel Base Control Terminal Connect to the motor U V W Circuit Board...

Страница 5: ...rameter setting 12 Load shortcircuit protection 13 Autorestart or incorrectwiring protection 14 Incorrect wiring protection of external control stopterminals Ambient Structure Place to be used Altitud...

Страница 6: ...cuit power supply or install an electromagnetic contactor between the input terminals R S T and the power supply to run or stop the motor soft starter Do select RUN or STOP keys on the operation panel...

Страница 7: ...k Terminal Name Functional Description Bypass Output Operation Output Delayed Switch on 01 and 02 after soft starter is completely started to control bypass contactor 03 and 04 indicate programmable r...

Страница 8: ...Start Common Port Switch K on motor starts switch K off motor stops Chapter 2 Installation and Wiring Instantaneous Stop Stop Start Common Port Instantaneous Stop Stop Start Common Port 2 3 6 Relay N...

Страница 9: ...ne stops completely 2 This key also performs the function of failure state resetting When REAdy is displayed press this key to set the manual When P0030 is displayed repress this key When flashes pres...

Страница 10: ...regardless of successor failure Note H1 H9 refer to save 9 recently occurred failure tips in a recursive way If entering setting mode in none soft start stop mode you may get tips Press then press to...

Страница 11: ...he current limiting value code P3 indicating current mode enabled to raise the torque Be sure the motor rotates in the correct direction Only after making sure there is no anomaly can the motor be put...

Страница 12: ...error report P2should be set to thismode if thesoft starter adoptsone to multi wiring method To extend the servicelife of softstarter free stop mode isgenerally preferred ifthere is no needto adopt so...

Страница 13: ...oltage but not through the mechanical control over time t regardless of whether the motor is accelerated steadily Therefore if there is a light load the starting time will tend to be less than the set...

Страница 14: ...rammable output external terminals changes from open toclose that is reversed phase output Flexible use ofprogrammable relay output functions cansimplify external control logic circuit Chapter 5 Descr...

Страница 15: ...the decisiondatum deviation willbe enhanced Overcurrent Starting ProtectionTime Thisrefers to theprotection time thatis successively 5 timeslonger than themaximum working currentset by thecode P4 See...

Страница 16: ...atment Fault cleared Faults such as undervoltage overvoltage overcurrent instantaneous terminal open etc have been eliminated Everything turns to normal and now the LED ready lights up indicating the...

Страница 17: ...tableabove are themaximum values ofa soft starter Generally ratedcurrent matching themotor that hassame power shouldnot excess therated current values listedin this table If outline sizesdiffer from t...

Страница 18: ...uality problem or accident we merely promise to bear the above mentioned responsibilities Ifa user needs more guarantees for liabilities please assure on the insurance company voluntarily Appendix 1 V...

Отзывы: