Installation 

- 80 - 

Notes: 

(1) Ensure quality of user supplied connecting pipe. Before connection, clean inside of pipe 
and prepare bell mouths. You can order these from our factory. 

(2) Site fabrication of bell mouths must use special pipe-expander to avoid F22 leak after 
installed. 

(3) Use two spanners to tighten connection between indoor unit and connecting pipe; 
otherwise indoor unit tubing may twist, deform or even break. 

4. Venting of system 

(1) Loosen nut on upper air pipe (large pipe) of outdoor unit large shutoff (ball) valve by half 
a round; 

(2) Unscrew valve core nut on the two valves; 

(3) Open small shutoff (or ball) valve core by one round. When you feel that air coming out of 
air pipe nut on the large shutoff (or ball) valve is cold, this means that air is basically vent. 
Immediately tighten air pipe nut with spanner. Then open both shutoff (ball) valve cores, put 
on valve core nuts and tighten. 

 

 

 

 

 

 

 

 

 

 

Note: Use of the unit without opening all valve cores will cause failure or poor performance

When ball valve core is rotated parallel to pipeline axis, the valve is open. 

 

5. System leakage detection 

(1) Fully open large and small shutoff (or ball) valve cores to detect leakage; confirm no 
refrigerant leakage; 

(2) Halogen mutual detection meter shall be used for detection, or apply soapy water at 
connections and valve cores etc.; 

(3) In case of slight leakage, use spanner to tighten leaking connection till the leak vanishes; 
otherwise it is necessary to correct threaded connector and bell mouth jointing face and 

Steam pipe

 

Valve core nut

Valve core nut

Loosen half round before venting

Large shutoff (ball) valve 
Small shutoff (ball) valve

 

Liquid pipe

 

For venting, unscrew nut
and open valve core by one
round

 

Содержание -B

Страница 1: ...Structure Features Air duct Type Air Conditioner Service Manual JIANGSU CHUNLAN REFRIGERATING EQUIPMENT Co Ltd AUGUST 2004...

Страница 2: ...ters 34 Chapter IV Performance curve 40 Chapter V Circuit diagrams 41 Chapter VI List of main parts and wear parts 59 Chapter VII Type selection 65 Chapter VIII Installation 66 Chapter IX Air duct des...

Страница 3: ...ion The product can be widely used in large area multi room composite compartment houses villa and medium and small restaurants bars leisure and recreation sites II Indoor unit 1 Indoor unit of low st...

Страница 4: ...pressure series air duct type air conditioner FR D 95 FR D 125 S indoor unit outline FR D 180 S FR D 260 S indoor unit outline Electric box Wire controller Remote controller Air exhaust Lifting lug mo...

Страница 5: ...II Outdoor units FRD23 B FRD35 B FRD50 B outdoor unit FRD71 B FR71 B outdoor unit FR D 95 FR D 125 S FR95 C FR125 C S FR D 100 B outdoor unit outline FR D 180 S outdoor unit outline FR D 260 S outdoor...

Страница 6: ...ter II Exploded views dismantling sequence of parts I Exploded view dismantling sequence of indoor unit of FRD23 B FRD35 B and FRD50 B 1 Exploded view of FRD23 B FRD35 B and FRD50 B indoor unit Explod...

Страница 7: ...lectric heater 7 Heat exchange section top plate assembly 8 Fan section left side plate assembly Optional 9 Impeller 10 Motor 11 Fan section top plate Optional 12 Fan section rear plate assembly Optio...

Страница 8: ...Indoor capacitor 1 Remove 12 2 Remove capacitor Indoors motor 1 Remove fan section rear plate 12 2 Remove fan section top plate 11 3 Remove spiral casing 13 and impeller 9 4 Remove connecting plug fro...

Страница 9: ...of parts 7 II Exploded view and dismantling sequence for outdoor unit of FRD23 B FRD35 B FRD50 B 1 Exploded view of outdoor unit of FRD23 B FRD35 B and FRD50 B Exploded view of outdoor unit of FRD23...

Страница 10: ...ssembly 2 Small shutoff valve 3 Large shutoff valve 4 Compressor 5 Axial flow fan 6 Motor 7 Reversing valve assembly 8 Left rear plate assembly 9 Handle assembly 10 Outdoor electric assembly 11 Top co...

Страница 11: ...cover assembly 11 2 Remove handle assembly 9 3 Remove left rear plate assembly 8 4 Remove outdoor electric assembly 10 Outdoors motor 1 Remove top cover assembly 11 2 Remote handle assembly 9 3 Remove...

Страница 12: ...ence of parts 10 III Exploded view and dismantling sequence of indoor unit of FR D 71 B and FR D 100 B 1 Exploded view of indoor unit of FR D 71 B and FR D 100 B Exploded view of indoor unit of FR D 7...

Страница 13: ...Left support 4 PTC electric heater Only for FRD71 B FRD100 B 5 Spiral casing 6 Impeller 7 Left side plate assembly 8 Evaporator assembly 9 Condensate tray assembly 10 Bottom plate assembly I 11 Botto...

Страница 14: ...ling sequence of typical parts Indoor capacitor 1 Remove 1 2 Remove capacitor Indoors motor 1 Remove electric box 18 2 Remove plug of indoor motor from control board in electric box 3 Remove air intak...

Страница 15: ...loded view dismantling sequence of parts 13 IV Exploded view and dismantling sequence of outdoor unit of FR D 71 B 1 FR D 71 B outdoor unit exploded view FR D 71 B outdoor unit exploded view Outdoor u...

Страница 16: ...t assembly 5 Condenser 6 Left panel 7 Top cover assembly 8 Air intake grating 9 Baffle plate assembly 10 Right panel assembly 11 Handle 12 Electric assembly 13 Valve support assembly 14 Reversing valv...

Страница 17: ...parts Outdoor electric assembly 1 Remove top cover assembly 7 2 Remove front plate assembly 1 3 Remove right panel assembly 10 13 4 Remove electric assembly 12 Outdoors motor 1 Remove top cover assem...

Страница 18: ...Exploded view dismantling sequence of parts 16 V Exploded view and dismantling sequence of indoor unit of FR95 C FR125 C S 1 Exploded view of indoor unit of FR95 C and FR125 C S...

Страница 19: ...mbly 5 Left support plate 6 Small side plate assembly 7 Fixing support assembly 8 Fixing support cover plate assembly 9 Spiral casing assembly 10 Centrifugal impeller 11 Strainer frame 12 Motor 13 Mot...

Страница 20: ...Remove 19 12 Remove 20 13 Remove 5 18 17 14 Remove 15 Annex Dismantling sequence of typical parts Indoor capacitor 1 Remove 1 2 Remove 11 14 3 Remove capacitor Indoors motor 1 Remove electric box 4 2...

Страница 21: ...ling sequence of parts 19 VI Exploded view and dismantling sequence of indoor unit of FR D 95 and FR D 125 S 1 Exploded view of indoor unit of FR D 95 and FR D 125 S Exploded view of indoor unit of FR...

Страница 22: ...ing strip 7 Left side plate assembly 8 Fixing block 9 Left small hole cover plate 10 Square hole cover plate assembly 11 Air intake 12 Bottom plate assembly 13 Impeller 14 Spiral casing assembly 15 Ta...

Страница 23: ...en tapping screws on retainer 26 rotate retainer 26 2 Remove right small hole cover plate assembly 10 3 Remove capacitor clip 20 Indoor motor 1 Loosen tapping screws on retainer 26 rotate retainer 26...

Страница 24: ...box of FRD95 and FRD125 S No Description Remark 1 Top plate 2 Frame assembly 3 Left side plate assembly 4 Bottom plate assembly II 5 Bottom plate assembly I 6 PTC electric heater 7 Right side plate as...

Страница 25: ...ling sequence of outdoor unit of FR D 95 FR D 125 S FR D 100 B FR95 C and FR125 C S 1 Exploded view of outdoor unit of FR D 95 FR D 125 S FR D 100 B FR95 C FR125 C S Exploded view of outdoor unit of F...

Страница 26: ...apillary assembly 7 T pipe assembly 8 Valve Dg8 9 Motor support 10 Flat washer 5 11 Spring washer 5 12 Motor 13 Nut M5 14 Axial flow fan 15 Front panel assembly 16 Handle 17 Electric assembly 18 Baffl...

Страница 27: ...uence of typical parts Outdoor electric assembly 1 Remove top cover 1 2 Remove right panel assembly 4 3 Remove cover plate on electric assembly 17 Outdoor motor 1 Remove top cover assembly 1 2 Remove...

Страница 28: ...nce of parts 26 IX Exploded view and dismantling sequence of indoor unit of FR D 180 S and FR D 260 S 1 Exploded view of indoor unit of FR D 180 S and FR D 260 S Exploded view of indoor unit of FR D 1...

Страница 29: ...ning strip 7 Left side plate assembly 8 Fixing block 9 Left small hole cover plate 10 Square hole cover plate assembly 11 Air intake 12 Bottom plate assembly 13 Impeller 14 Spiral casing assembly 15 T...

Страница 30: ...ole cover plate assembly 10 3 Remove capacitor clip 20 Indoors left motor capacitor seen from air exhaust 1 Remove 1 2 Remove capacitor clip 20 Indoor motor 1 Remove 1 2 Remove 14 3 Same method as for...

Страница 31: ...oded view dismantling sequence of parts 29 X Exploded view and dismantling sequence of outdoor unit of FR D 180 S 1 FR D 180 S outdoor unit exploded view FR D 180 S outdoor unit exploded view Outdoor...

Страница 32: ...lary assembly 7 Manifold assembly 8 Valve Dg10 9 Motor support 10 Flat washer 5 11 Spring washer 5 12 Motor 13 Nut M5 14 Axial flow fan 15 Front panel assembly 16 Handle 17 Electric assembly 18 Cover...

Страница 33: ...ypical parts A Outdoor electric assembly 1 Remove top cover 1 2 Remove right panel assembly 4 3 Remove cover plate 18 on electric assembly 17 B 1 Remove top cover assembly 1 2 Remove left panel assemb...

Страница 34: ...dismantling sequence of parts 32 XI FR D 260 S outdoor unit exploded view and dismantling sequence 1 FR D 260 S outdoor unit exploded view and dismantling sequence FR D 260 S outdoor unit exploded vie...

Страница 35: ...ir intake pipe assembly 1 9 LP valve assembly 1 29 Right air exhaust pipe assembly 1 10 Bolt M8 30 12 30 Connector assembly 1 11 Washer 8 12 31 Right side plate assembly 1 12 Spring washer 8 32 Air wa...

Страница 36: ...Mass Outdoor unit kg 28 35 52 Indoor unit dB A 38 44 48 Noise Outdoor unit dB A 50 52 56 Refrigerant kg R22 0 71 R22 1 24 R22 1 6 Liquid pipe mm 6 Connecting pipe size Air pipe mm 10 12 Air exhaust si...

Страница 37: ...ting 2420W 3100W Cooling 13 4A 17 8A Rated input current Heating 11 8 A 11 8 10 5 A 14 2 A 14 2 10 5 A Air circulation flow 1500 m3 h 2000 m3 h Air exhaust static pressure 30Pa Indoor unit noise 54dB...

Страница 38: ...Main technical parameters 36 3 Value in is nominal value for auxiliary electric heating...

Страница 39: ...Indoor unit noise 52dB A 54dB A Outdoor unit noise 62dB A 64dB A R22 filling amount 2 95Kg 3 2Kg Climate type T1 Remote control Yes Indoor unit 47Kg 52Kg Mass Outdoor unit 85Kg 95Kg Liquid pipe 10 1 L...

Страница 40: ...6Pa 127Pa Indoor unit noise 61dB A 64dB A Outdoor unit noise 62dB A 64dB A R22 filling amount 2 95Kg 3 2Kg Climate type T1 Remote control Yes Indoor unit 35Kg 43Kg Mass Outdoor unit 85Kg 95Kg Liquid p...

Страница 41: ...air static pressure 76Pa 127Pa Indoor unit noise 63dB A 66dB A Outdoor unit noise 65dB A 68dB A R22 filling amount 5 8Kg 11 5Kg Climate type T1 Remote control Yes Indoor unit 65Kg 46 85Kg 62 Mass Out...

Страница 42: ...static pressure performance curve 1 Air flow static pressure performance curve for FR D 71 B FR D 100 B FR D 95 and FR D 125 S 2 Air flow static pressure performance curve of FR D 180 S and FR D 260...

Страница 43: ...Circuit diagrams 41 Chapter V Circuit diagrams I Circuit diagrams...

Страница 44: ...Circuit diagrams 42...

Страница 45: ...Circuit diagrams 43...

Страница 46: ...Circuit diagrams 44...

Страница 47: ...Circuit diagrams 45...

Страница 48: ...Circuit diagrams 46...

Страница 49: ...Circuit diagrams 47...

Страница 50: ...Circuit diagrams 48...

Страница 51: ...Circuit diagrams 49...

Страница 52: ...Circuit diagrams 50...

Страница 53: ...Circuit diagrams 51...

Страница 54: ...Circuit diagrams 52...

Страница 55: ...Circuit diagrams 53...

Страница 56: ...Circuit diagrams 54...

Страница 57: ...contactor coil L Phase line feedline of power cable user supplied N Zero line feedline of power cable user supplied L Phase line of indoor outdoor connecting cable of power connecting cable user suppl...

Страница 58: ...door connecting cable user supplied outdoor fan motor high speed 2 Indoor outdoor connecting cable user supplied outdoor fan motor medium speed 3 Indoor outdoor connecting cable user supplied reversin...

Страница 59: ...C S and FRD125 S signal line terminals 1 Outdoor fan motor high speed 2 Outdoor fan motor medium speed 3 Reversing valve coil 4 Compressor AC contactor coil N Power supply zero line L1 3 phase power...

Страница 60: ...Circuit diagrams 58 2 Gray Outdoors tube temperature sensor 3 Purple HP pressure controller 4 Orange LP pressure controller 5 Black Phase sequence 1 6 White Phase sequence 2 7 Brown Overcurrent...

Страница 61: ...W 020 07 50 2 5 FAC 450V Comm line RF10W FG 000 01 OD PT probe wire FRD35 D 000 01 MC Compressor YZG 25RT1 YZG 39RCT1 SHX33SC4 U MF2 OD fan motor FRD35W 100 00WX FRD50W 080 01WX Axial flow fan FRD35W...

Страница 62: ...h YK 3 1 2 25 M1 Outdoor fan motor YDK5120 30 6 YDK1120 45 6 C2 Capacitor Startup capacitance 6 F AC 450V M2 Compressor Q2 2 ZR47K3 PFJ M M Indoor fan motor YDK110 30 4 YDK5110 30 4 FU Indoor fuse 5A...

Страница 63: ...8 F AC 450V C3 Capacitor CBB65A 60 F AC 450V C4 Capacitor CBB65A 1K 50 F AC450V Communication line RF10AW FG 000 01 RF10AW FG 000 01 OD pipe temp probe line RF10AW FG 000 02 RF10AW FG 000 02 M1 Outdoo...

Страница 64: ...Capacitor CBB65A 1K 50 F AC450V Communication line RF10AW FG 000 01 RF10AW FG 000 01 OD pipe temp probe line RF10AW FG 000 02 RF10AW FG 000 02 M1 Outdoor fan motor YDK3120 45 6 YDK2120 45 6 M2 Compre...

Страница 65: ...7 List of main parts wear parts of FR180 S and FR260 S Size Model Symbol Description FR D 180 S FR D 260 S PCB1 Main control board PCB2 Wire controller PCB3 Remote controller RT1 Temperature sensor 33...

Страница 66: ...62 00 8 List of special main parts wear parts for FRD180 S FRD260 S aux electric heating Size Model Symbol Description FRD180 s FRD260 S PCB1 Main control board FT1 2 3 4 5 6 1 time fuse 153 10A 153 1...

Страница 67: ...nstaller or designer is unaware of the relation between static pressure and noise level and fails to select proper model user may think that high static pressure air duct type air conditioner has low...

Страница 68: ...ased on FR260 S Outdoor unit Indoor unit Air delivery pipeline Air delivery port Branch air return port Air return port Wire controller Connecting pipeline Medium static pressure air duct air conditio...

Страница 69: ...bject to potential hazard before installation Position of installation shall ensure shortest connecting hose between indoor and outdoor units and length of indoor air duct shall be suitable Sufficient...

Страница 70: ...68 FR D 95 FR D 125 S a mm b mm c mm d mm e mm FR D 95 655 300 698 FR D 125 S 865 400 618 330 908 FR D 71 B FR D 100 B Code Model a mm b mm c mm d mm e mm FR D 71 B 1200 1160 1230 FR D 100 B 1820 226...

Страница 71: ...Installation 69 FR95 C FR125 C S FR D 180 S FR D 260 S Code Model A mm B mm C mm D mm E mm F mm FR D 180 S 1309 300 654 1352 FR D 260 S 1800 618 400 330 888 1843...

Страница 72: ...ing hook on indoor unit Use 4 M10 expansion bolts to fix lifting hook on bearing mounting face 2 Installation mode for other models based on FR180 S and FR260 S The following is an ideal installation...

Страница 73: ...ust air port inside the machine 1 Auxiliary electric heater installation dimensions Refer to the following figure and table for installation dimensions of FRD95 FRD125 S FRD180 S and FRD260 S auxiliar...

Страница 74: ...not be lower than required in the figure below Avoid low place where water can accumulate A location where piping of indoor and outdoor units and power cables can be easily arranged to facilitate ins...

Страница 75: ...ation 2 Installation of outdoor unit To avoid center of gravity offset and protect compressor never tilt the machine by more than 45 degrees during transportation Use M12 bolts to fix machine chassis...

Страница 76: ...strictly follow instruction manual When arranging rain shelter do not affect heat dissipation of the machine IV Installation of air duct 1 The following shows a number of typical installation modes fo...

Страница 77: ...duct shall meet specification In case of noise requirement by user follow relevant requirements described in air duct design and noise reduction sections of this manual 3 Recommended distance from mai...

Страница 78: ...d one fresh air port is provided at each side of the unit and can be open to needs Refer to installation mode 3 for fresh air port arrangement for FR D 95 FR D 125 S FR D 71 B FR D 100 B FR D 180 S an...

Страница 79: ...justment can be made according to height of indoor ceiling Return air grating with washable air strainer must be installed to prevent dust from entering the unit Recommended distance between return ai...

Страница 80: ...team to avoid change of position and installation mode of installed indoor unit keep indoor unit condensate pipe clean and reserve maintenance openings for future maintenance V Installation of LCD wir...

Страница 81: ...and drain pipe so as to prevent ingress of rainwater and air 2 Installation of condensate drain pipe 1 Condensate drain pipe shall be normal PVC pipe of 16 17 inner diameter FR95 C FR125 C S water dis...

Страница 82: ...air is basically vent Immediately tighten air pipe nut with spanner Then open both shutoff ball valve cores put on valve core nuts and tighten Note Use of the unit without opening all valve cores will...

Страница 83: ...R D 95 FR D 125 S FR95 C FR125 C S FR D 180 S FR D 260 S Recommended max length m 15 20 20 20 20 Recommended max HGTdiff m 5 8 8 8 10 Recommended max elbows 3 5 5 5 5 When length and height exceed abo...

Страница 84: ...h normal operation reverse compressor rotation can cause high noise and small current FR D 180 S and FR D 260 S wire controller will indicate E6 confirm no absent phase for reverse compressor rotation...

Страница 85: ...t and air port air speed according to state codes and standards Product installation and operation manual and Chunlan design code for home commercial centralized air conditioning system Data in follow...

Страница 86: ...peed Remark Orifice 3 5 Seam port 2 4 Spout 4 10 Upper limit is preferred for high even delivery requirement or hot air for high installed position of port or higher air speed is allowed in area of pe...

Страница 87: ...higher user requirement on noise silencers shall be installed on air delivery return ducts a Resistive silencer By means of sound absorbing material stuck on inner wall of air duct sound energy propag...

Страница 88: ...rom environment and rooms that require quietness The unit can be can be installed in special equipment room toilet storeroom or other ancillary rooms If this is not feasible make sure to contact our q...

Страница 89: ...product samples for preliminary determination of air port size 3 Calculate air resistance in air delivery return systems Further verify correct type selection of air duct and ports by referencing uni...

Страница 90: ...ght tube branch tube elbow or air port for particular type selection reference manufacturer product samples 4 Increase thickness of air duct wall and wrap ultra fine glass wool or other sound absorbin...

Страница 91: ...ating status With unit in operating status press power ON OFF key will stop the unit and place it in standby status After pressing power ON OFF key if power supply is interrupted and resumed the unit...

Страница 92: ...erate in set mode and timing status automatically changes to normal operation Time setting is 01 24h Initial value is 01 interval is 1h and this setting will increase 1h every time the timing key is p...

Страница 93: ...ess this key to decrease temperature by 1 degree Temperature setting range is 12 32 when temperature display is 12 temperature decrease key is not functional when temperature display is 32 temperature...

Страница 94: ...to polarity requirement in battery chamber Close batteries cover by pushing upward Notes 1 Use 2 5 1 5V batteries do not mix different batteries 2 Remove batteries if the remote controller will not be...

Страница 95: ...ower than current indoor temperature otherwise the unit will be in ventilating mode b If ambient is too high cooling load will be too high so that set temperature won t be met c For your health and po...

Страница 96: ...n installation position and environment Frequently clean indoor strainer to avoid failure Indoor units of FR D 95 FR D 125 S FR D 180 S FR D 260 S FR95 C and FR125 C S are complete with strainer Indoo...

Страница 97: ...n E8 E8 E8 E8 Low pressure protection E9 In case of repeated protections of air conditioner cut off power supply and have failure corrected by specialty maintenance personnel before restarting the mac...

Страница 98: ...shooting 1 Neither indoor unit nor outdoor unit operating Phenomena Possible causes Correction method Power outage Restore power supply Transformer burnt down Locate fault repair replace transformer S...

Страница 99: ...a Possible causes Correction method Neither outdoor fan nor compressor operating at Cooling or Heating OD control board relay coil broken wire or bad contact Replace relay OD fan motor failure or dama...

Страница 100: ...in long operation will reduce air cycle and lower evaporator heat exchange efficiency hence cooling effect Clean strainer to remove dust and let it dry in cool air before reinstallation Dust accumula...

Страница 101: ...ng HP and LP etc Replace compressor Bad thermal insulation of indoor outdoor unit connecting pipe Apply separate thermal insulation for bid and small pipes Reversing valve failure Replace reversing va...

Страница 102: ...Replace with insulated pipe or wrap drain pipe with insulation Clogged or broken drain pipe Clean or replace drain pipe Wrapping of pipe connector not tight dewing Wrap tight Water leakage in indoor c...

Страница 103: ...or if normal check if R7 on ID board is 10K ID pipe temp probe broken wire short circuit Wire controller displays E3 put it into operation after re powerup First check ID pipe temperature sensor conne...

Страница 104: ...main control board damage No heating function Check for normal temperature sensor RT1 Check for normal DC12V DC5V power supply Check for reliable output port connection of compressor reversing valve I...

Страница 105: ...n wire short circuit Wire controller displays E3 only put it to operation after re powerup First check for bad contact in indoor pipe temperature sensor connection Check for broken wire or short circu...

Страница 106: ...or bad contact at ID OD connecting cable Check for damaged OD board current transformer Load relief protection Wire controller displays E8 only put it to operation after re powerup Check for normal co...

Страница 107: ...r intact fan capacitors Outdoor fan failure Check for intact connection of outdoor unit wiring terminal Check for damaged main control board Check for intact outdoor fans Check for intact fan capacito...

Страница 108: ...r re powerup First check ID pipe temperature sensor connection for bad contact check for broken wire or short circuit in sensor if normal check if R6 on ID board is 10K OD pipe temp probe broken wire...

Страница 109: ...V batteries Check crystal oscillator circuit Check for normal transmitter Check for displaced or bad contact in conducting rubber No cooling function Check for normal temperature sensor RT1 Check for...

Страница 110: ...tion Check for intact indoor fans Check for intact fan capacitors Outdoor fan failure Check for intact connection of outdoor unit wiring terminal Check for damaged main control board Check for intact...

Страница 111: ...ch hose leading 2 lines of right angle bends This branch hose was 20cm diameter round corrugated plastic hose and total air delivery cross sectional area was less than 0 1 m2 hence air delivery side w...

Страница 112: ...es noise level is apparently high 2 Unit installed on support angle steel by hard contact causes resonance and hard contact between metal air duct and ceiling running water pipe aggravates the resonan...

Страница 113: ...ol boards and wire controllers of two units the same protections occurred on the same unit Analysis According to past maintenance experience main control board manufactured before 2002 and used in hum...

Страница 114: ...r complained about poor cooling and heating effect Analysis 1 There were a total of 3 air delivery ports one was too near and the other two had small delivery speed 2 Incorrect air delivery angle Solu...

Страница 115: ...air delivery port had high noise Analysis 1 Fixing of indoor unit did not follow instruction manual requirements 2 Distance between return air box and ceiling was only 12cm and return air space was t...

Отзывы: