Maintenance Manual
37
PEFS F3 Maintenance Manual, Version 1.2, Feb 2018
© Copyright 2017 Chubb Fire & Security Pty Ltd
Type
Image
Part No.
Description
Nipple
112150
7/16” JIC Bulkhead
112148
1/4” NPT x 7/16” JIC
128817
1/8” NPT x 7/16” JIC
118542
1/8” NPT
Adaptor
93696
1/8” BSPT x 7/16” JIC (f)swv
129579
¼” NPT x 7/16” JIC (f)swv
Insulated P-
Clip
Size
Maximum
Spacing (m)
128819
¼” Tube
0.5
103197
¼” Hose
1/4”
0.5
103198
Use with Grommet 103248
0.5
130078
¼” Hose with hose protector
0.5
Grommet
103248
Grommet to hold LOP tubing.
Use with P-Clip 103198.
Weld Lug
129578
M8 Weld Lug c/w bolt and washer for
mounting P-Clips
Table 16
– PEFS F3 pneumatic actuation hose and tube fittings
Monitoring Components
Pressure Switches
“Cylinder low pressure”, 1550kPa NO setting DT04-3P (part number 137060)
“Fire Alarm/Discharge”, 200kPa NC setting DT04-2P (part number 87041)
Figure 19
– Pressure Switches