Installation
12
Linear Plus Series User Instruction Manual
Cable Sizes and
Current
The following table indicates the recommended sizes of conductors in accordance with the NEC
®
. (Air
temperature surrounding the conduits not greater than 86°F (30°C).)
NOTE:
Cable sizes are suggested and based on standard configurations. Installers should verify correct
conductor sizes pursuant to NEC
®
and/or state or local codes. If the installation requires long conductor
runs, consult NEC
®
and/or state or local codes to account for electrical losses.
Table 4. Cable Sizes
Term ID
Description
6 kVA (4 kVA)
10 kVA (8 kVA)
main wire
gauge (awg
term torque
(in-lbs)
min wire
temp (°C)
*
main wire
gauge (awg
term torque
(in-lbs)
min wire
temp (°C)*
JMP
JL1
Line 1 (Jumper)
‡
8
40
75
6
45
75
JL2
Line 2 (Jumper)
‡
8
40
75
6
45
75
MAIN
ML1
Line 1 (Main)
8
40
75
6
45
75
ML2
Line 2 (Main)
8
40
75
6
45
75
E/G
Chassis Ground
**
40
75
**
45
75
BYPASS
BL1
Line 1 (Bypass)
8
40
75
6
45
75
BL2
Line 2 (Bypass)
8
40
75
6
45
75
E/G
Chassis Ground
**
40
75
**
45
75
OUTPUT
‡‡
X1
Output Term 1
10
35
75
6
45
75
X2
Output Term 2
10
35
75
6
45
75
X3
Output Term 3
10
35
75
6
45
75
E/G
Chassis Ground
10
35
75
6
45
75
X4
Output Term 4
10
35
75
6
45
75
X5
Output Term 5
10
35
75
6
45
75
X6
Output Term 6
10
35
75
6
45
75
‡ Wire between JL1 & BL1 and between JL2 & BL2 if only single input power source is used.
‡‡ Output voltage available at output terminals dependent on specific model. See Table 5 - 7 on page 13 for details.
* Use insulated copper wire rated 75°C minimum
** Must be no smaller than wire connected to L1 and L2
NOTE: For installation per IEC regulations
: If installing units per regulations IEC-287 and DIN VDE 0298, 6 kVA model
should be wired (inputs and outputs) with 6 mm
2
cable torqued to 4.5 nt-m; and 10kVA model (inputs and outputs) should be
wired with 10 mm
2
cable torqued to 5.0 nt-m. (Based on 70°C cable and ambient of 30°C)
Содержание Linear Plus LPBP610-2
Страница 10: ...Setup Linear Plus Series User Instruction Manual 5 Fig 1 Step 1 Remove Strapping Fig 2 Step 2 Lift Crate 2 1 ...
Страница 43: ...Appendix B Paralleling UPS Devices Linear Plus Series User Instruction Manual 39 ...
Страница 44: ...Appendix B Paralleling UPS Devices 40 Linear Plus Series User Instruction Manual ...