45
Motor shutdown mode
Slow
shutdown/fr
ee shutdown
1. The starting mode of the main frequency converter is to
start and stop the communication.
Slow down: when the factory parameter is set as deceleration,
the controller receives the stop command, the loading valve is
disconnected, the controller sends the deceleration stop
command to the frequency converter, and the frequency
converter slows down according to the set deceleration time.
Free stop: when the stop mode in the factory parameter is set
as free stop, the controller receives the stop command, the
loading valve is disconnected, the controller sends the frequency
write command through 485 communication port, and the
frequency of frequency converter is decreased.
Send the stop command to the frequency converter 1 second
before the downtime delay countdown is completed.
2. The starting mode of the main frequency converter is the
starting and stopping time of the terminal.
Slow down: when the stop mode in the factory parameter is
set as deceleration, the controller receives the stop command,
the loading valve is disconnected, the main frequency converter
operation terminal is disconnected, and the frequency converter
slows down according to the set deceleration time.
Free stop: when the stop mode in the factory parameter is set
as free stop, the controller receives the stop order, the loading
valve disconnects, the operating terminal of the main engine
frequency converter remains closed, and the frequency of the
control converter drops.
Disconnect 1 second before downtime delay countdown is
completed.
Main Frequency
converter Starting
mode
Communicati
on
on-off/port
on-off
Communication start and stop: start frequency converter
through RS485 communication. Terminal start andstop:by
switching onandofffrequency converter.
Note:
1: the controller setting parameters should be in line withthe
frequencyconverter startandstopmode. 2:whentheuserneedsto
switchVariableFrequency, terminal 12 is used as the input
control terminal of the converter, and the controller can only start
and
stop the converter by means of communication.
Communication start
Frequency converter
times
06
After the controller sends the opening command to the frequency
converter, it is found that the frequency converterdoes not execute
the running command, and the maximum number of setting times is
repeatedtoopenthe
command.
Содержание Quan Wei
Страница 1: ...TaiWan QuanWei Screw type air compressor Using and Maintenance Instructions ...
Страница 12: ...8 ...
Страница 81: ...77 ...
Страница 82: ...78 8 2 2 QWL 15A 20A 8 2 3 QWL 30A 40A ...
Страница 83: ...79 8 2 4 QWL 50A 60A ...
Страница 84: ...80 8 2 5 QWL 75A 100A ...
Страница 85: ...81 8 2 6 QWL 150A 175A ...
Страница 86: ...82 9 0 Circuit diagram ...
Страница 87: ...83 9 1 MAM 860 880 Circuit diagram 9 2 MAM 890 Circuit diagram ...
Страница 88: ...84 9 3 MAM 6080 Circuit diagram ...
Страница 89: ...85 Screw Air Compressor operation record tale ...