NWC1 Series Self-healing Low Voltage Shunt Capacitors

4

.

3

 

The

 

capacitors

 

are

 

placed

 

in

 

the

 

capacitor

 

compensation

 

cabinet

 

which

 

should

 

provide

 

the

 

following

 

protection

 

measures

See

 

Table

 

4

 

for

 

details

.

Table

 

4

 

Capacitor

 

protection

 

measures

 

in

 

cabinet

Protective

 

characteristics

Name

 

and

 

function

 

of

 

support

 

devices

Typical

 

models

Transient

 

overvoltage

 

protection

Zinc

-

oxide

 

surge

 

arrestor

 

or

 

surge

 

protector

FYS

-

0

.

28

 

or

 

NU6

-

2

 

Transient

 

overcurrent

 

protection

Capacitor

 

dedicated

 

contactor

current

 

limiting

 

reactor

or

 

smart

 

compound

 

switch

 

with

 

zero

-

cross

 

detection

CJ19

XD1

 

or

 

ZCK

 

Steady

 

stage

 

overvoltage

 

protection

Generally

compensation

 

controller

 

can

 

provide

 

overvoltage

 

protection

.

NWK1

-

G

NWKL1

Steady

 

stage

 

overcurrent

 

protection

Thermal

 

relay

 

or

 

capacitor

 

switch

 

with

 

overcurrent

 

protection

 

function

.

JR36

 

or

 

ZCK

 

Short

 

circuit

 

protection Choose

 

fast

 

acting

 

fuse

 

for

 

short

 

circuit

 

protection

For

 

capacitors

 

with

 

capacity

30kvar

user

 

can

 

use

 

miniature

 

circuit

 

breaker

 

for

 

short

 

circuit

 

protection

For

 

capacitors

 

with

 

capacity

 ≥

30kvar

miniature

 

circuit

 

breaker

 

is

 

not

 

recommended

.

RT36

 

or

 

NT00

        

NWC1

 

series

 

square

 

case

 

products

 

consist

 

of

 

fully

 

independent

 

units

 

with

 

automatic

 

protection

 

functions

The

 

units

 

use

 

cylindrical

 

stretched

 

aluminum

 

enclosure

 

while

 

the

 

case

 

is

 

made

 

of

 

cold

-

roll

 

steel

 

sheets

This

 

structure

 

provides

 

double

 

protection

 

which

 

eliminate

 

the

 

risks

 

of

 

explosion

 

and

 

leakage

 

and

 

guarantees

 

safety

See

 

Figure

 

1

-

4

 

below

 

for

 

outline

 

and

 

installation

 

dimensions

.

  

5

 

Main

 

Features

Outline

 

and

 

Installation

 

Dimensions

  

67

 H

 H

+3

4.5

194

25 25

224

206

41

Φ 6× 10

Figure 1 (1-20) kvar outline and installation dimensions

3-M6

132

224

254

Φ 12× 16

Figure 2 (22-40) kvar outline and installation dimensions

3-M8

 H

H

+

41

194

28 28

132

 350

380

Φ 12× 20

320

300

80

375

80

Figure 3 (45-60) kvar outline and installation dimensions

3-M12

380

350

Φ

12× 20

196

320

300

375

80

80

3-M2

Figure 4 (80-100) kvar outline and installation dimensions

Содержание NWC1 Series

Страница 1: ...Standard IEC 60831 1 2014 IEC 60831 2 2014 NO 2021 01 NWC1 Series Self healing Low Voltage Shunt Capacitors ...

Страница 2: ...maintenance 2 Installation in any damp condensed phase environment with inflammable and explosive gas is forbidden 3 When the product is being installed or maintained the power must be switched off 4 You are prohibited from touching the conductive part when the product is operating ...

Страница 3: ...ation Commissioning and Operation Main Features Outline and Installation Dimensions Analysis and Troubleshooting of Faults Maintenance and Storage Product Selection and Ordering Information 11 Environmental Protection 01 01 01 02 04 04 06 06 07 08 08 Use Purpose and Application Range Warranty Period Environmental Protection and Law Regulations ...

Страница 4: ...wer electronic equipment frequency converter energy saving transformation such as motor speed regulation variable frequency air conditioner etc DC rectifier inverter electrolytic plating equipment electric arc furnace and intermediate frequency furnace etc See Table 1 for capacitor selection and harmonic suppression measures under harmonic environment 3 Conditions for Normal Use Installation and T...

Страница 5: ...overvoltage 1 1UN no more than 8h of continuous operation within 24h Maximum allowable overcurrent 1 3IN no more than 2h of continuous operation within 24h Short time 2 0IN Self discharge characteristics Residual voltage drops from 2UN to 75V DC or below within 3min after power off Ambient temperature 25 50 25 C Customizable 40 50 Relative temperature 50 at 40 90 at 20 Altitude m 2000 Tightening t...

Страница 6: ... fuse for short circuit protection For capacitors with capacity 30kvar user can use miniature circuit breaker for short circuit protection For capacitors with capacity 30kvar miniature circuit breaker is not recommended RT36 or NT00 NWC1 series square case products consist of fully independent units with automatic protection functions The units use cylindrical stretched aluminum enclosure while th...

Страница 7: ...ng lug See Table 6 for the selection of conductor sectional area Figure 5 Capacitor installation drawing Table 5 Installation spacing and safety distance Capacity kvar Minimum installation spacing S1 mm Safety distance at the top of capacitors S2 mm 1 20 30 50 22 32 50 50 35 100 80 50 6 4 Preparation and inspection before use 6 4 1 Before using the capacitor user should check if the model on the n...

Страница 8: ...orage 7 1 Daily maintenance and calibration Check if the operating current of the capacitor is normal by using the amperemeter and compensation controller in the cabinet Check if there is any deformation oil leakage and overheating Abnormalities such as overcurrent and overtemperature caused by harmonic will reduce the service life of the capacitor and can cause damage to other components and cond...

Страница 9: ...ms are typical when the grid harmonic is too big or there is intermittent resonance in the grid Conduct grid harmonic test or check if there are harmonic sources such as frequent converter rectifier intermediate frequency furnace or electric arc furnace installed at load end See 3 3 2 for harmonic suppression measures 5 Sometimes there is buzzing sound in the cabinet during operation There is harm...

Страница 10: ...tment process or be sent to the recycling station for assortment dismantling and recycling according to local regulations In order to protect the environment the product or product parts should be disposed of according to the industrial waste treatment process or be sent to the recycling station for assortment dismantling and recycling according to local regulations 10 1 User should provide produc...

Страница 11: ...08 NWC1 Series Self healing Low Voltage Shunt Capacitors DR J03 NWC1 Series Self healing Low Voltage Shunt Capacitors IEC 60831 1 2014 IEC 60831 2 2014 ...

Страница 12: ...NWC1 Series Self healing Low Voltage Shunt Capacitors User Instructions ...

Отзывы: