NVF5 Series User Manual
Appendix B Parameter list
Code
Name
Setting Range
Default
Change
Fd .38
Fan Running Elapsed
Time
0
~
Max.65535Hours
0
●
Fd .39
Rated Capacity
(
0
~
999.9
)
kVA
(
Depend On
Series
)
Set By
Factory
●
Fd .40
Rated Voltage
(
0
~
999
)
V
(
Depend On
Series
)
Set By
Factory
●
Fd .41
Rated Current
(
0
~
999.9
)
A
(
Depend On
Series
)
Set By
Factory
●
Fd.42
Serial Type
Range:0x0000~0xFFFF
0x0500
●
Fd .43
Software Version
0.00
~
99.99
1.00
●
Fd .44
Customized Version
0
~
99.99
1.00
●
Fd .45
Source Code
Compilation Year
2014
~
2099
2017
●
Fd .46
Source Code
Compilation Date
101
~
1231
101
●
Fd.47
Setting RPM
(
0 ~ 60000
)
rpm
0
●
Fd .48
Current Running Time
(
1 ~ 65535
)
min
0
●
Fd .49
Rest Running Time
(
0 ~ 65535
)
H
0
●
Fd .50
Power Factor Angle
0.1 ~ 20.0
0
●
Fd .51
VF Separated Target
Voltage
(
0.0 ~ 100.0
)
%
(
Motor Rated
Voltage
)
0.0%
●
Fd .52
VF Separated Output
Voltage
(
0.0 ~ 100.0
)
%
(
Motor Rated
Voltage
)
0.0%
●
Fd .53
Inverter GP Type
0 ~ 3
0
●
Fd .54
Motor Temperature
(
1~200
)
℃
0
℃
●
FE Protection and Early Alarm Group
FE.00
Motor Overload
Protection Selection
0
:
Ineffective
1
:
Effective
1
○
FE.01
Motor Overvoload
Protection Gain
0.20
~
10.00
1.00
○
FE.02
Motor Overload Early
Alarm Enable
0
:
Ineffective
1
:
Effective
0
○
FE.03
Motor Overload Early
Alarm Level
(
20
~
200
)
%
80%
○
FE.04
Overvoltage Stall
Protection Selection
0
:
Ineffective
1
:
Effective
2
:
Effective in Decel.Mode
0
○
FE.05
Overvoltage Stall Gain
0
~
100
(
0
:
Prohibit
)
0
○
FE.06
Overvoltage Stall
Protection Voltage
(
120
~
150
)
%
130%
○
FE.07
Overcurrent Stall Gain
0
~
100
(
0
:
Prohibit
)
20
○
FE.08
Overcurrent Stall
(
100
~
200
)
%
150%
○
- 136 -