Appendix B Parameter list
Code
Name
Setting Range
Default
Change
F0 Basic Program Group
F0.00
Motor Control Mode
0
:
Sensorless Vector Control
1
:
Reserve
2
:
V/F Mode
2
◎
F0.01
Command Source
0
:
Integral Keypad
1
:
Digital Terminal
2
:
Communication
3
:
Remote Panel
0
○
F0.02
Main
Frequency
Reference
0
:
Digital Given
1
:
AI1
2
:
AI2
3
:
Reserve
4
:
High Speed Pulse HDI
Reference
5
:
Preset Speed Reference
6
:
Simple PLC Reference
7
:
Close Loop PID Reference
8
:
Reserve
9
:
Potentiometer Reference
0
○
F0.03
Auxiliary Frequency
Source Option
Same as F0.02
(
Main Frequency
Reference
)
0
○
F0.04
Main Aux. Frequency
Source Computing
Ones Place
:
Frequency Source
Selection
0
:
Main Frequency Ref.
1
:
Computing Result
Tens Place
:
Main Aux.
Frequency Source Computing
0
:
Main + Aux.
1
:
Mian – Aux.
2
:
MAX(the bigger one of
both)
3
:
MIN(the smaller one of
both)
0x0000
○
F0.05
Digital Given
F0.09
~
F0.08
5.00Hz
○
F0.06
Direction Setting
0
:
Default Direction
1
:
Reverse Enable
2
:
Reverse Disable
0
○
F0.07
Max. Output
Frequency
F0.08
~
600.00Hz
50.00 Hz
◎
F0.08
Maximum Frequency
F0.09
~
F0.07
50.00 Hz
○