−7−
5.1.3 Noise preventive terminals
Separate the communications cable from drive power cables and other communications cable more
than 50cm so as not to be affected by noises.
5.1.4 Crimp style terminals
Falling off of connections is one of communications
failures. Terminate the communications cable with an [O]
or [Y] type crimp style terminal having an insulation sleeve.
(The terminal screws of LT830 controllers and line
converters are M3.5mm.)
5.1.5 Mount an insulation resistor
For using the RS-485 communications interface, mount a 100
Ω
resistor to the LT830 controller
connected at the final end. (For details, see Section 5.3)
[A general metal film resistor can be used. The resistor (sold separately) is available at CHINO.]
5.1.6 Number of LT230 controllers connectable
For RS-485: Up to 31 sets
Insulation sleeves
O type crimp terminal
3.7 more
7 or less
3.7 more
7 or less
Y type crimp terminal
Insulation sleeves
(mm)