6.8 Table of Input types & SV_Dot
(Table 5. List of input types.)
Input type
Input type(ºC)
SV
DOT
B
0 to 1820 0
R 0
to
1760
0
S 0
to
1760
0
N 0
to
1300
0
K1 –200
to
1370 0
K2 –199.9
to
500.0
0
E –199.9
to
700.0
1
J –199.9
to
900.0
1
T/C
T –199.9
to
400.0
1
PT1001 –199.9
to 850.0 1
RTD
PT1002 –199.9
to 200.0 1
Input type
Range
DC
voltage
5V
0.000 to 5.000
0 to 3
6.9 Remote SV Setting Through Communication
6.9.1
Digital communications between LT and LT controllers
(Between CHINO’s controller and LT)
Set the communication function at communications transmission [t r S] and communications remote
[r e M], then digital communication can be done between LT and LT.
(
Details: See
□
7
Communications Transmission and Communications Remote
)
In this case, LT8 that is set at communications remote will receive all types of remitted data (PV, SV)
as remote SV.
6.9.2 Personal Computer Communi Communications Remote Functions
There will be the case that it needs to receive the remote SV in a connecting condition of personal
computer and LT8 (communication function is CoM.). In this case, keep the communication function
[CoM] and write SV data on reference no.49512 (remote SV), and it will become to receive remote SV
with receiving measuring data between personal computer and LT8 and sending & receiving of
parameter. This case of receiving data of remote SV works as remote SV data that is same as
communications remote (6.9.1).