5. Description of Function Code
EM12-SP User Manual
26
FE-33
detection time of full-water
protection
0 - 30000sec
10sec
FE-34
exit time of full-water
protection
0 - 30000sec
60sec
FE-35
analog sensor damaged
Thresholds
0 - 100.0%
0.0%
FE-31 is for Full-water detection mode.
If set to 0, set any terminals(default DI4/DI5)function code to 51/52
,
two terminals enabled in same time could
activate Full-water protection and two terminals disabled in same time could activate exit Full-water protection.
One of the terminals enabled, remains its status without any change.
FE-33/FE-34 for detection time of full-water protection and exit time of full-water protection;
FE-35 for analog sensor damaged Thresholds
,
if FE-31 set to analog detection, and analog feedback is larger than
the setting detectionThreshold value of FE-35. Judge it as analog sensor faults. Display A.Prb, and stop running;
FE-31 set to 0, close sensor faults detection.
FE-36
PV DC correction coefficient
0.0 - 200.0%
100.00%
FE-37
PV DC correction offset
-100.00A - 100.00A
0.00A
As software estimating solar cells’ DC current value, this parameters will correction this estimation value, U0-06
displays correction current, correction formula is U0-06 =(estimation value * FE-36)+ FE-37
;
FE-38
power curve point 0
0.0kw - 999.9kw
0.5kw
FE-39
power curve point 1
0.0kw - 999.9kw
1.0kw
FE-40
power curve point 2
0.0kw - 999.9kw
1.5kw
FE-41
power curve point 3
0.0kw - 999.9kw
2.0kw
FE-42
power curve point 4
0.0kw - 999.9kw
2.5kw
FE-43
flow curve point 0
0.0 - 999.9m^3/h
0.0 m^3/h
FE-44
flow curve point 1
0.0 - 999.9m^3/h
5.0 m^3/h
FE-45
flow curve point 2
0.0 - 999.9m^3/h
10.0m^3/h
FE-46
flow curve point 3
0.0 - 999.9m^3/h
15.0m^3/h
FE-47
flow curve point 4
0.0 - 999.9m^3/h
20.0m^3/h
According output power(U0-05) calculate output flow speed(U0-13), User reference(P-Q curve), input to FE-38
~
FE-47, software automatically calculate U0-13
;
Generally, P-Q curve as below:
]
/
[
3
h
m
Q
]
[
KW
P
Diagram 5-5 P-Q curve