3. Installation of Frequency Inverter
EM12-SP User Manual
8
3.4.2 Control Circuit Terminal Layout
+
10V
AI1
AO1
485+
DI1
DI2
DI3
DI4
DI5
HDI
GND
AI2
AO2
485-
GND COM CME COM +24V COM
TA
TB
TC
FM
DO1 COM
Diagram3-3 EM12-SP control circuit terminal sketch diagram
3.4.3 Description of control circuit terminals
Type
Terminal
Symbol
Terminal Name
Terminal function description
Power
Supply
+10V-GND
Ex10V
power supply
P10V power supply to external unit. Maximum
output current:10Ma
Generally, it provides power supply to external
potentiometer with resistance range of 1
kΩ
~
5kΩ
+24V-COM
Ex24V
power supply
P24 V power supply to external unit. Generally, it
provides power supply to DI/DO terminals and external
sensors. Maximum output current: 200 mA
PLC
External power
supply input
terminals
It connect with +24V default
Analog
input
AI1-GND
Analog input
terminal 1
1. Input range: DC 0V~10V/ 0mA~20mA, decided by
jumper JP2 on the control board
2. Impedance: 22 kΩ (voltage input), 500 Ω (current input)
AI2-GND
Analog input
terminal 2
1. Input range: DC 0V~10V/ 0mA~20mA, decided by
jumper JP3 on the control board
2. Impedance: 22 kΩ (voltage input), 500 Ω (current
input)
Digital
input
DI1
Digital input 1
1. Optical coupling isolation, compatible with dual polarity
input
2.Input
Impedance: 2.4 kΩ
3. Voltage range for level input: 9V~30 V
DI2
Digital input 2
DI3
Digital input 3
DI4
Digital input 4
DI5
Digital input 5
DI6
Digital input 6
HDI
High Speed Pulse
Input Terminal
Besides features of DI1~DI5 and it can be used for
high-speed pulse input.
Maximum input frequency: 50 kHz
Analog
output
AO1-GND
Analog output
terminal 1
Voltage or current output is decided by jumper JP4.
Output voltage range: 0V~10 V
Output current range: 0mA~20 mA
AO2-GND
Analog output
terminal 2
Output voltage range: 0V~10 V
Relay
output
TA1/2-TB1/2
NC terminal
Contact driving capacity: 250 VAC, 3 A, COSø = 0.4
DC 30 V, 1 A
TA1/2-TC1/2
NO terminal
J2
External keypad
interface
External keypad